Power and Control Wiring

10

The input and output power wire size should be based on the upstream overcurrent protection device,

observing the NEC and local codes.
The molded case switches contained in the STS2 are typically non-automatic circuit breakers that

rely on the upstream and/or load overcurrent protection. Upstream overcurrent protection should be

rated equal to or less than the rating of the STS2 molded case switches.
The STS2 input and output power and ground and neutral bus bars accommodate a wide range of

wire sizes. The STS2 bus bars accommodates standard 2 hole lugs.

5.2

Input Junction Box Installation (Optional)

The input junction box option is available to simplify input connections to the STS2. Two input junc-

tion boxes and the associated flexible 10 foot long (3 meter) input cables are provided with this option.
This option is available only with bottom cable entrance, typically when the unit is located on a raised

floor.
If the input junction boxes will be used, they either can be shipped with the unit or shipped in

advance to be installed during the rough-in stage of construction.
Locate the junction boxes a maximum of 8 feet (2.4 meters) from the planned location of the Static

Switch.
Due to a lack of clearance for the cables below the unit, the cables are also shipped loose from the unit

for installation at the site. The input cables connect from the input junction boxes to the input power

bus bars inside the STS2.
The standard configuration for the input junction boxes and cables is for 3-wire-plus-ground feeds. If

the input neutral is required, special 4-wire-plus-ground input cables and junction boxes are required.

See Figure 30 for wiring details.
For preparation purposes, the following tables provide the dimensions and wire sizes for the input

junction boxes.

Table 3

Input/output conduit plate specifications

Rating

Max. number and size

100-250A

6 — 3" conduit

400-600A

9 — 4" conduit

800-1000A

12 — 4" conduits

Table 4

Input junction box dimensions

Switch Rating

Length

Inches (mm)

Width

Inches (mm)

Height

Inches (mm)

100 amp

16 (406)

14 (356)

6 (152)

250 to 600 amp

30 (762)

16 (406)

6 (152)

Table 5

Input junction box terminal wire size range

Switch Rating

Power and Ground Lug Wire Range

100 amp

#6 to #2/0 AWG

250 to 600 amp

(2) #6 AWG to (2) 500 kcmil