Table 19. ni 9211 scan list format, Ni 9213, Table 20. ni 9213 vendor configuration extensions – National Instruments Deterministic Ethernet Expansion Chassis NI 9144 User Manual

Page 32

Advertising
background image

NI 9144 User Guide and Specifications

32

ni.com

Table 19 contains the default scan list.

NI 9211 Calibration Data

Calibration data is set up by the driver during initialization, and the
calibration conversion is performed on the module ADC itself.

NI 9213

Table 19. NI 9211 Scan List Format

Index

Sub

Type

Value

0x2001

0

ARR:U32

7

1

6

2

0

3

1

...

...

7

5

Table 20. NI 9213 Vendor Configuration Extensions

Index

Sub

Type

R/W

Description

0x2001

0

ARR:U32

Scan List = 19

1

R

Channels to Convert = 1..18, default = 18

2..19

R/W

Channel Code

0x2002

1

ARR:U32

R/W

Conversion Speed Control = 2 or 15, default = 2

0x2003

0

U32

R

Common Mode Range Error Detection Status
(also as 8-bit PDO)