Table 37. ni 9219 scan list format, Table 38. ni 9219 conversion time value – National Instruments Deterministic Ethernet Expansion Chassis NI 9144 User Manual

Page 43

Advertising
background image

© National Instruments Corporation

43

NI 9144 User Guide and Specifications

NI 9219 Configuration Command

Whether you are using the channel or not, you must configure the
Conversion Time, Mode, Range, and Calibration Gain/Offset values for
each channel on the NI 9219.

Note

You must first send calibration gain and offset values in MSB format. The

Conversion Time value must be the same across all channels.

Where:

Table 37. NI 9219 Scan List Format

Bits

Field

7:6

Channel Number, 0..3

5

= 0

4:0

Configuration Type

Table 38. NI 9219 Conversion Time Value

Configuration Type

Value

Conversion Time

0x1F

Mode & Range

0x01

Calibration Offset 2 (LSB)

0x06

Calibration Offset 1

0x05

Calibration Offset 0 (MSB)

0x04

Calibration Gain 2 (LSB)

0x0A

Calibration Gain 1

0x09

Calibration Gain 0 (MSB)

0x08

Advertising