NI 9219 Configuration Commands

There are eight configuration commands for the NI 9219.
Eight configuration commands must be sent for each of the four channels.
This is true even if you are only using a subset of the four channels. Each
of the eight configuration commands is 1 Byte, each configuration
command is followed by a data Byte, and then by a CRC value, which is
1 Byte. Hence, 3 Bytes * 8 Commands * 4 channels = 96 command bytes
(held in 32 entries in the object dictionary).

Data in the object dictionary is held in LSB format, so the value
0x12345678 is represented in memory as the series of bytes 0x78, 0x56,
0x34, 0x12. The command word format is shown in Table 36.

NI 9219 CRC Calculation

U8 crcShiftReg = 0;

for ( x = 0 ; x < 8 ; ++x )

{

dataBool = ((0x80>>x) & configCommand) != 0;

shiftBool = (0x01 & crcShiftReg) != 0;

crcShiftReg /= 2;

if (dataBool != shiftBool)

crcShiftReg ^= 0x8C;

}

for ( x = 0 ; x < 8 ; ++x )

{

dataBool = ((0x80>>x) & configData) != 0;

shiftBool = (0x01 & crcShiftReg) != 0;

crcShiftReg /= 2;

if (dataBool != shiftBool)

crcShiftReg ^= 0x8C;

}

crcShiftReg = crcShiftReg << 1;

return crcShiftReg;

Table 36. NI 9219 Command Word Format

Bits

Field

31:24

Reserved

23:16

CRC

15:8

Configuration Data

7:0

Configuration Command