Table 33. ni 9219 adc format field format – National Instruments Deterministic Ethernet Expansion Chassis NI 9144 User Manual

Page 39

Advertising
background image

© National Instruments Corporation

39

NI 9144 User Guide and Specifications

NI 9219 ADC Format

The NI 9219 converts at different rates, and can specify different data
formatting styles. This is determined by both the ADC Format field and
corresponding fields in the setup commands. The format of the ADC
Format field is shown in Table 33.

Standard values for ADC Format are:

0x0001000F, High-Speed

0x000B000F, Best 60 Hz Rejection

0x000D000F, Best 50 Hz Rejection

0x0032000F, High-Resolution

0x2100

0

ARR:U32

Calibration = 168

1

R

Ch0 60 V Offset

2

R

Ch0 60 V Offset

3

R

Ch0 15 V Offset

...

...

...

42

R

Ch0 Full Bridge 7.8m V–V Gain

43

R

Ch1 60 V Offset

...

...

...

0x2101

0

ARR:U32

Q

External Calibration = 168

1

R

Ch0 60 V Offset

...

...

...

...

...

Table 33. NI 9219 ADC Format Field Format

Bits

Field

31:24

Reserved

23:16

Conversion speed in multiples of 10 mS

15:8

Reserved

7:0

AI Data Formatting

Table 32. NI 9219 Vendor Configuration Extensions (Continued)

Index

Sub

Type

R/W

Description

Advertising