Frequency generation, Using the frequency generator, Figure 7-27. frequency generator block diagram – National Instruments Network Device DAQ S User Manual

Page 95: Figure 7-28. frequency generator output waveform, Frequency generation -23, Using the frequency generator -23

Advertising
background image

Chapter 7

Counters

© National Instruments Corporation

7-23

NI 6124/6154 User Manual

Frequency Generation

You can generate a frequency by using a counter in pulse train generation
mode or by using the frequency generator circuit.

Using the Frequency Generator

The frequency generator can output a square wave at many different
frequencies. The frequency generator is independent of the
two general-purpose 32-bit counter/timer modules on S Series devices.

Figure 7-27 shows a block diagram of the frequency generator.

Figure 7-27. Frequency Generator Block Diagram

The frequency generator generates the Frequency Output signal. The
Frequency Output signal is the Frequency Output Timebase divided by a
number you select from 1 to 16. The Frequency Output Timebase can be
either the 20 MHz Timebase divided by 2 or the 100 kHz Timebase.

The duty cycle of Frequency Output is 50% if the divider is either 1 or
an even number. For an odd divider, suppose the divider is set to D.
In this case, Frequency Output is low for (D + 1)/2 cycles and high for
(D – 1)/2 cycles of the Frequency Output Timebase.

Figure 7-28 shows the output waveform of the frequency generator when
the divider is set to 5.

Figure 7-28. Frequency Generator Output Waveform

100 kHz Timebase

20 MHz Timebase

Frequency

Output

Timebase

FREQ OUT

Divisor

(1–16)

Frequency Generator

÷

2

Frequency

Output

Timebase

FREQ OUT

(Divisor = 5)

Advertising