5-2 Parameter Description

Zone output function

To use the zone output function, the desired zone must be specified with point data. (See
Chapter 7, "EDITING POINT DATA".) When the robot enters the specified zone, its re-
sult is output to the specified port. Point numbers and output port that can be used for each
zone output are listed below.

Zone setting range and output port

Zone No.

P900-P901

P902-P903

P904-P905

P906-P907

Zone 0

Zone 1

Zone 2

Zone 3

Specified range

Output port

DO0

DO1

DO2

DO3

c

CAUTION

The zone output function does not work if one item of the point data is unspecified or return-to-origin is
incomplete.

Example

q

DO0

OFF

ON

OFF

Current
position

100.00

200.00

PRM53=1 (Zone 0 output enabled, positive logic output)

P901=200.00

P900=100.00

Example

w

DO2

ON

OFF

ON

Current
position

100.00

200.00

PRM53=68 (Zone 2 output enabled, negative logic output)

P905=200.00

P904=100.00