3-Phase Synchronization and Signal Wiring

TM-DIOP-01XN-01

2-19

3-Phase Synchronization and Signal Wiring

Refer to Table 2-2 for the signal pinouts.

To achieve proper three-phase output, units configured for each phase
need to be wired to the appropriate phase. Extra care should be exercised
when multiple paralleled units are also wired for 3-phase operation. In
this case it is advisable to group all parallel inverters belonging to the
same phase together in a rack.

First ensure power to the rack has been disconnected. Make
connections to the CAN/SYNC connector using its screw-type wire
clamps. It may be necessary to remove the mating connector to
facilitate connections to the terminal.

Twisted bundles of four multi-colored wires should be used for easier
identification.

Start with unit in Phase-1, wire from “SYNC-OUT 0” in this phase to
“SYNC-OUT 120” of Phase-2 and “SYNC-OUT 240” of Phase-3.

Next, Connect a different color wire from “SYNC-OUT 120” of
Phase-1 to “SYNC-OUT 240” of phase-2 and “SYNC-OUT 0” of
Phase-3.

Connect a different color wire from “SYNC-OUT 240” of Phase-1 to
“SYNC-OUT 0” of phase-2 and “SYNC-OUT 120” of Phase-3.

Lastly, connect all “RETURN” lines together.

See section on “Parallel Operation” on page 2–15 to connect
additional units to each phase.

Figure 2-10 3-Phase Sync Connection

1

4

7

5

3

6

2

L1
L2

L1
L2

2

6

3 5 7

4

1

4

7

5

3

6

2

1

L2

L1