Inverter Module Installation and Operation

3-8

TM-DIOP-01XN-01

Overload Protection

The inverter will deliver the rated load power continuously at the rated
ambient temperature. It will also reliably operate up to 1600 Watts
without further restriction on the maximum ambient temperature. The
internal temperatures of critical components monitored by the DSP will
determine operating time at this overload range. Beyond 1600 Watts, the
DSP computes the power and extrapolates the operating time at that
power level before shutting down. The maximum overload rating is
3000 Watts for 5 seconds. After each overload trip event, the inverter
re-starts after a 10-second pause. Should three such events occur within a
2-minute interval, the inverter shuts down permanently. Normal operation
can be restored by clearing the alarm (see “To Clear an Alarm” on
page 3–11) or us
ing the front panel switch.

Figure 3-3 Overload curve

OVERLOAD OPERATION

0

500

1000

1500

2000

2500

3000

3500

0

5

10

15

20

Time (s)

Output Power (W)