Operating Instructions

TM-DIOP-01XN-01

4-19

Automatic Shutdown Email

When the inverter shuts down due to a fault or a user shutdown, the
Ethernet interface will attempt to send an email to the configured “Email
Alert Address” using the configured “SMTP Server” (see “Network
Connection” on page 4–9).

Contents of the email:

From: XDI <serial number>

To: <Email Alert Address>

Subject: Unit has shutdown

Body:

Serial # <Serial> at <IP> has shutdown. <Shutdown_Code>

The shutdown code list is a list of decimal values that represent specific
shutdown conditions (Table 4-7, “Shutdown Code” on page 4–19)
currently exhibited by the inverter. Each shutdown code is separated by a
space.

Important:

By the time you have received the email, if the inverter has

shutdown due to a fault, the inverter may have already corrected the problem.

Table 4-7 Shutdown Code

Code

Fault Description

16

Reserved

15

Reserved

14

Reserved

13

Input stage voltage out of range

12

DC link stage over voltage

11

Output stage over voltage

10

Multiple output stage over current

9

Output overload

8

Synchronization error

7

Over temperature

6

Output disabled via interlock

5

Output disabled via interface command

4

Output disabled by user.

(To enable, toggle interlock or interface command)

3

DC link stage under voltage

2

Output stage under voltage

1

Output stage over current