User interface, Front panel, User lines – Xantrex Technology XDI2048 User Manual

Page 48: User interface –6, Front panel –6 user lines –6, Table 3-1, Front panel led functions –6, Table 3-2, User line pins –6, Front panel user lines

Advertising
background image

Inverter Module Installation and Operation

3-6

TM-DIOP-01XN-01

User Interface

Front Panel

User Lines

The port with user lines is located at the rear panel of the rack mount
frame (Figure 2-3). See Figure 2-7. The following table lists the signals:

Table 3-1 Front Panel LED Functions

Red LED

Green LED

Function

ON

OFF

A continuously incompatible operating condition
exists and an alarm has tripped. See “Protections
and Alarms” on page 3–7). The
inverter is
automatically turned off until the fault/alarm has
been cleared.

OFF

ON

Regular operating conditions. Output is on and
delivering power.

OFF

fast flashing

Self-Diagnostic mode. Prior to enabling the
inverter the unit always performs a self-check and
diagnostics.

OFF

slow-short flash Stand-by mode.

Table 3-2 User Line Pins

Pin Name

Function

1

User_Ground

All user lines are referenced to user_gnd. User_gnd is
isolated from both the input DC power and the output AC
power.

2

Shut_Down

This is an input pin. The input impedance is 100

Ω in

parallel with 20 pF. A logic high (1.25 V to 5 V) would set
the inverter into Standby Mode (see page 3–5). If pin 2 is
floating, the internal pull_down resistor of 100

Ω will

force a logic “0” and this pin becomes inactive.

3

Fault_Flag

This is an output pin. A logic high (5 V) indicates that an
alarm has tripped. The output of the inverter is, therefore,
disabled.

4

Auxiliary_Line This is an output pin. The functionality of this user line is

factory preset. It can be user configured if the Ethernet
option is installed.

5

Inverter_On

This is an output pin. A logic high (5 V) indicates that the
inverter is in an “on” state and delivering AC power to the
AC output power terminal.