Inverter specifications, Electrical specifications, Inverter – Xantrex Technology XDI2048 User Manual

Page 80: Specifications

Advertising
background image

Specifications

A-2

TM-DIOP-01XN-01

Inverter

Specifications

Electrical Specifications

Input Voltage, Current, Power, Frequency Ranges

Output Voltage, Current, Power, Frequency Ranges

Nominal Input

- 48 VDC

Input Range

- 40 to - 60 V (meets all specification)

Safe Input Range

± 80 Vdc (will not damage unit)

Maximum Input Current

90 A (at 40 V in, max 3 kW surge output,
5 s max)

Nominal input Current

36 A (at 48 V input, 1500 W output)

Maximum Input Current Ripple

< 1% Input Current

DC Side Voice Band Noise Limit

less than 32 dBrnc (C-message
weighting)

Over Current Protection

electronic limit on input boost converter
stage, 60 A fuse on DC input Inverter
stage output fuse for extreme faults

Inrush Current Controlled

40 A typical at 48 V < (2x I

rated

)

Waveform

True Sinusoidal

THD

< 3% Typical for linear loads

Output Voltage

120 Vac/60 Hz
230 Vac/50 Hz

Voltage Regulation

< -10%/+4% over full operating range

Frequency Stability

± 0.05%

Frequency Accuracy

60/50 Hz ± 0.1%

Fully Isolated

input to output

Power Rating

2 kVA/1.5 kW Max, over full operating
temperature range

Peak Output Current Into
Nonlinear Load

50A

pk

maximum for 120VAC

25A

pk

maximum for 230VAC

Advertising