Regulatory approvals, Environmental specifications – Xantrex Technology XDI2048 User Manual

Page 82

Advertising
background image

Specifications

A-4

TM-DIOP-01XN-01

Efficiency

•

Minimum 85% efficiency at full power, peak efficiency 89%

•

No load draw: less than 60 W

Start Up
Behavior

•

Hot-Swap capable, with controlled inrush current

•

No arcing of connectors when unit inserted or withdrawn

•

Output phase locked to parallel connected units prior to power up

•

Smooth balancing of power with parallel connected units.

Regulatory Approvals

CE EMC Directive requirements FCC Part 15 Class B radiated and
conducted limits.

NEBS LEVEL 3

120 V, 60Hz:

Certified to CAN/CSA C22.2 No. 60950-00 and

UL60950, 3rd Ed. and carries the cCSAus mark. Complies with FCC Part
15, Subpart B, Class B (radiated and conducted emissions.)

230 V, 50Hz:

Carries CE mark and complies with the Low Voltage

Directive and EN60950. Complies with the specific requirements of both
EN55022 (emissions) and EN55024 (immunity).

Environmental Specifications

Operating Ambient Temperature

0° (32°F) to +50°C (122°F), no de-rating

Storage Temperature Range

-50° (-58°F) to +85°C (185°F)

Humidity Range

Max 95% non-condensing