Operation and checkout, Operation, Checkout – Grain Systems PNEG-526 User Manual

Page 167: Motor operation checkout

Advertising
background image

63-2202—4 B.B. Rev. 11-00

www.honeywell.com

Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.

SERIES 72 MODUTROL IV™ MOTORS

Home and Building Control Home and Building Control

Honeywell Asia Pacific Inc. Honeywell Europe S.A.

Honeywell Latin American

Honeywell

Honeywell Limited-Honeywell Limitée

Room 3213-3225

3 Avenue du Bourget

Region

1985 Douglas Drive North

35 Dynamic Drive

Sun Hung Kai Centre

1140 Brussels

480 Sawgrass Corporate Parkway

Golden Valley, MN 55422

Scarborough, Ontario

No. 30 Harbour Road

Belgium

Suite 200

M1V 4Z9

Wanchai

Sunrise FL 33325

Hong Kong

OPERATION AND CHECKOUT

Operation

The motor feedback potentiometer and control current input
circuit form a bridge circuit. As long as the final control
element remains at the position proportional to the input
current from the controller, the circuit is balanced, and the
motor does not run. When the value of the controlled medium
changes, the current from the controller changes, and
unbalance is amplified to energize the Triac switching to run
the motor in the proper direction to correct the change in the
temperature or the pressure. The motor turns the feedback
potentiometer to rebalance the circuit and stop the motor.

Checkout

After installation and linkage adjustment, operate the motor
through the controller. Make sure that:

The motor properly operates the damper or valve.

The motor responds properly as the input is varied.

The auxiliary switch, if used, operates at the desired point
of motor rotation.

Inspect the motor, linkage, and valve or damper to see that all
mechanical connections are correct and secure.

In damper installations, the pushrod should not extend more
than a few inches past the ball joints. Check to see that
there is adequate clearance for the linkage to move through
its stroke without binding or striking other objects.

See controller or system instructions for additional checkout
procedures.

Motor Operation Checkout

Check motor operation as follows:

1.

To close the motor, open terminals +, -, and F.

2.

To open the motor, connect terminal F to the
negative (-) motor terminal.