Specifications, fuses and circuit breakers, English-3 – Grain Systems PNEG-526 User Manual

Page 83

Advertising
background image

English-3

Specifications, Fuses and Circuit Breakers

Drive Ratings

Catalog
Number

Output Ratings

Input Ratings

Branch Circuit Protection

Power
Dissipation

kW (HP)

Amps

Voltage
Range

kVA Amps Fuses

140M Motor
Protectors

(2)

Contactors

IP20 Open
Watts

100 - 120V AC (±10%) – 1-Phase Input, 0 - 230V 3-Phase Output
22A-V1P5N104 0.2 (0.25)

1.5

90-126

0.75

6.0

10

140M-C2E-C10 100-C09

25

22A-V2P3N104 0.4 (0.5)

2.3

90-126

1.15

9.0

15

140M-C2E-C16 100-C12

30

22A-V4P5N104 0.75 (1.0)

4.5

90-126

2.25

18.0

30

140M-D8E-C20 100-C23

50

22A-V6P0N104 1.1 (1.5)

6.0

90-126

3.0

24.0

40

140M-D8E-C25 100-C37

70

200 - 240V AC (±10%) – 1-Phase

(1)

Input, 0 - 230V 3-Phase Output, NO BRAKE

22A-A1P4N103 0.2 (0.25)

1.4

180-265

0.7

3.2

6

140M-C2E-B40 100-C09

25

22A-A2P1N103 0.4 (0.5)

2.1

180-265

1.05

5.3

10

140M-C2E-B63 100-C09

30

22A-A3P6N103 0.75 (1.0)

3.6

180-265

1.8

9.2

15

140M-C2E-C16 100-C12

50

22A-A6P8N103 1.5 (2.0)

6.8

180-265

3.4

14.2

25

140M-C2E-C16 100-C16

75

22A-A9P6N103 2.2 (3.0)

9.6

180-265

4.8

19.6

30

140M-D8E-C25 100-C23

100

200 - 240V AC (±10%) – 1-Phase

(1)

Input, 0 - 230V 3-Phase Output

22A-A1P5N104 0.2 (0.25)

1.5

180-265

0.75

5.0

10

140M-C2E-B63 100-C09

25

22A-A2P3N104 0.4 (0.5)

2.3

180-265

1.15

6.0

10

140M-C2E-B63 100-C09

30

22A-A4P5N104 0.75 (1.0)

4.5

180-265

2.25

10.0

15

140M-C2E-C16 100-C12

50

22A-A8P0N104 1.5 (2.0)

8.0

180-265

4.0

18.0

30

140M-D8E-C20 100-C23

80

200 - 240V AC (±10%) – 3-Phase Input, 0 - 230V 3-Phase Output
22A-B1P5N104 0.2 (0.25)

1.5

180-265

0.75

1.8

3

140M-C2E-B25 100-C09

25

22A-B2P3N104 0.4 (0.5)

2.3

180-265

1.15

2.5

6

140M-C2E-B40 100-C09

30

22A-B4P5N104 0.75 (1.0)

4.5

180-265

2.25

5.2

10

140M-C2E-C10 100-C09

50

22A-B8P0N104 1.5 (2.0)

8.0

180-265

4.0

9.5

15

140M-C2E-C16 100-C12

80

22A-B012N104

2.2 (3.0)

12.0

180-265

5.5

15.5

25

140M-C2E-C16 100-C16

115

22A-B017N104

3.7 (5.0)

17.5

180-265

8.6

21.0

35

140M-F8E-C25 100-C23

165

380 - 480V AC (±10%) – 3-Phase Input, 0 - 460V 3-Phase Output
22A-D1P4N104 0.4 (0.5)

1.4

340-528

1.4

1.8

3

140M-C2E-B25 100-C09

30

22A-D2P3N104 0.75 (1.0)

2.3

340-528

2.3

3.2

6

140M-C2E-B40 100-C09

40

22A-D4P0N104 1.5 (2.0)

4.0

340-528

4.0

5.7

10

140M-C2E-B63 100-C09

60

22A-D6P0N104 2.2 (3.0)

6.0

340-528

5.9

7.5

15

140M-C2E-C10 100-C09

90

22A-D8P7N104 3.7 (5.0)

8.7

340-528

8.6

9.0

15

140M-C2E-C16 100-C16

145

Input/Output Ratings

Approvals

Output Frequency: 0-240 Hz (Programmable)
Efficiency: 97.5% (Typical)

Digital Control Inputs (Input Current = 6mA)

Analog Control Inputs

SRC (Source) Mode:

18-24V = ON
0-6V = OFF

SNK (Sink) Mode:

0-6V = ON
18-24V = OFF

4-20mA Analog: 250 ohm input impedance
0-10V DC Analog: 100k ohm input impedance
External Pot: 1-10k ohms, 2 Watt minimum

Control Output (Programmable Output, form C relay)

Resistive Rating: 3.0A at 30V DC, 125V AC and 240V AC

Inductive Rating: 0.5A at 30V DC, 125V AC, and 240V AC

Recommended Fuses and Circuit Breakers

Fuse: UL Class J, CC, T or Type BS88; 600V (550V) or equivalent. Circuit Breakers: HMCP or Bulletin 140U or equivalent.

Protective Features

Motor Protection: I

2

t overload protection - 150% for 60 Secs, 200% for 3 Secs (Provides Class 10 protection)

Overcurrent: 200% hardware limit, 300% instantaneous fault
Over Voltage:

100-120V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 150V AC incoming line)
200-240V AC Input – Trip occurs at 405V DC bus voltage (equivalent to 290V AC incoming line)
380-460V AC Input – Trip occurs at 810V DC bus voltage (equivalent to 575V AC incoming line)

Under Voltage:

100-120V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 75V AC incoming line)
200-240V AC Input – Trip occurs at 210V DC bus voltage (equivalent to 150V AC incoming line)
380-480V AC Input – Trip occurs at 390V DC bus voltage (equivalent to 275V AC incoming line)

Control Ride Through: Minimum ride through is 0.5 Secs - typical value 2 Secs
Faultless Power Ride Through: 100 milliseconds

Dynamic Braking

Internal brake IGBT included with all ratings except No Brake versions. Refer to Appendix B of the PowerFlex 4 User Manual
on CD for ordering information.

(1)

200-240V AC - 1-Phase drives are also available with an integral EMC filter. Catalog suffix changes from N103 to N113

and N104 to N114.

(2)

Refer to the Bulletin 140M Motor Protectors Selection Guide, publication 140M-SG001… to determine the frame and

breaking capacity required for your application.

UL

®

UL508C
CSA 22.2
No. 14

C

US

EMC Directive 89/336/EEC, LV Dir. 73/23/EEC
LV:

EN 50178

EMC: EN 61800-3

Advertising