Tower Dryer Operations & Service

TROUBLESHOOTING

31

Problem

What to do

Pilot will not light.
(Continued)

- If pilot still doesn’t light, check pilot area on burner. Clean if necessary.
- If pilot area is hot indicating that the pilot was lighting, replace flame rod.
- If pilot area is cold, replace spark plug.
- If pilot still doesn’t light, check the Protectofier components in the control box.

Pilot lights but main burner

- Check for water in gas train by opening drain valve.

will not light

- Maxon valve should offer some resistance when opening. If it doesn’t,
check latching solenoid inside Maxon valve.
- Check for broken or bent butterfly valve.
- Check to make sure burner ports around the pilot are clean.

Dryer will not reach operating

- Increase gas pressure on main gas regulator.

temperature.

- Make sure dryer is completely full of grain.
- Gas ports on burner need to be drilled. Clean by using a #43 drill bit.
- Check to make sure butterfly valve is fully opening.
- Check for water in gas train by opening drain valve.

Plenum temperature fluctuates.

- Gas pressure is to high. Lower gas pressure on main gas regulator.

Dryer loses flame at regular

- Loose or dirty flame rod. Clean and/or tighten.

intervals while running.

- Defective Protectofier SS3CP transformer in control box. Replace.

Modulating Valve

- Check to see that Maxon shutoff valves are open.

does not open.

- Check to see that the plenum setpoint temperature is higher than the ambient

temperature.

- Check to see that 120VAC is being provided to the black and white wires in

the modutrol motor.

- Check the operation of the modutrol motor be momentary jumping the “F” and
“-“ terminals in the motor to see if the motor will open.

TROUBLESHOOTING – GENERAL

Problem

What to do

Control power switch

- Check to see that main circuit breaker in power box is on.

will not light.

- Check fuses “F1”, “F2”, “F3” in power box.

- Check circuit breaker “CB-04” in power box.
- Check MicroLogix PLC in control box.

OIU fails to light.

- Check to see that main circuit breaker in power box is on.

- Check fuses “F1”, “F2”, “F3” in power box.
- Check circuit breaker “CB-04” in power box.

Dryer shuts down, red light lights

- Check for possible fire in heat section of dryer.

and horn sounds, display shows:

- Make sure the plenum high limit control is set at least 30

° above the desired

“OVERHEAT AT PLENUM”

drying temperature.

“POSSIBLE FIRE”

- Check for a malfunctioning gas train component that could be causing excessive
plenum temperatures.