Power wiring, I/o wiring recommendations, I/o terminal block specifications – Grain Systems PNEG-526 User Manual

Page 84: English-4

Advertising
background image

English-4

Power Terminal Block (A Frame Shown)

Power Terminal Block Specifications

Input Power Conditions

I/O Terminal Block Specifications

Refer to the PowerFlex 4 User Manual on CD for maximum power and
control cable length recommendations

Power Wiring

Power Wire Rating

Recommended Copper Wire

Unshielded 600V, 75°C (167°F) THHN/THWN

15 Mils insulated, dry location

Shielded 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2

Belden 29501-29507 or equivalent

Shielded Tray rated 600V, 75°C or 90°C (167°F or 194°F) RHH/RHW-2

Shawflex 2ACD/3ACD or equivalent

V/T2

T/L3

S/L2

R/L1

U/T1

W/T3

BR+

BR-

Terminal

Description

R/L1, S/L2

1-Phase Input

R/L1, S/L2, T/L3

3-Phase Input

U/T1

To Motor U/T1

=

Switch any two motor leads to
change forward direction.

V/T2

To Motor V/T2

W/T3

To Motor W/T3

BR+, BR-

Dynamic Brake Resistor Connection [0.75 kW (1 HP) ratings and higher]

Safety Ground - PE

Frame

Maximum Wire Size

(1)

Minimum Wire Size

(1)

Torque

A

3.3 mm

2

(12 AWG)

0.8 mm

2

(18 AWG)

1.7-2.2 N-m (16-19 lb.-in.)

B

5.3 mm

2

(10 AWG)

1.3 mm

2

(16 AWG)

(1)

Maximum/minimum sizes that the terminal block will accept - these are not recommendations.

Input Power Condition

Corrective Action

Low Line Impedance (less than 1% line reactance)

Install Line Reactor

(2)

or Isolation Transformer

Greater than 120 kVA supply transformer

Line has power factor correction capacitors

Line has frequent power interruptions

Line has intermittent noise spikes in excess of 6000V (lightning)

Phase to ground voltage exceeds 125% of normal line to line voltage

Remove MOV jumper to ground.

or Install Isolation Transformer with
grounded secondary if necessary.

Ungrounded Distribution System

(2)

Refer to Appendix B of the PowerFlex 4 User Manual on CD for accessory ordering information.

I/O Wiring Recommendations

(3)

Wire Type(s)

Description

Minimum Insulation Rating

Belden 8760/9460
(or equiv.)

0.8 mm

2

(18AWG), twisted pair, 100% shield with

drain.

300V
60 degrees C
(140 degrees F)

Belden 8770
(or equiv.)

0.8 mm

2

(18AWG), 3 conductor, shielded for

remote pot only.

(3)

If the wires are short and contained within a cabinet which has no sensitive circuits, the use of shielded wire may not be
necessary, but is always recommended.

Maximum Wire Size

(4)

Minimum Wire Size

(4)

Torque

1.3 mm

2

(16 AWG)

0.13 mm

2

(26 AWG)

0.5-0.8 N-m (4.4-7 lb.-in.)

(4)

Maximum / minimum that the terminal block will accept - these are not recommendations.