Mount the drive upright on a flat, vertical and level surface.

Install on 35 mm DIN Rail.
or

Install with screws.

Protect the cooling fan by avoiding dust or metallic particles.

Do not expose to a corrosive atmosphere.

Protect from moisture and direct sunlight.

Minimum Mounting Clearances

Ambient Operating Temperatures

Refer to the PowerFlex 4 User Manual on the CD supplied with the
drive for details on how to comply with the Low Voltage (LV) and
Electromagnetic Compatibility (EMC) Directives.

Mounting Considerations

Minimum Panel Thickness

Screw Size

Mounting Torque

1.9 mm (0.0747 in.)

M4 (#8-32)

1.56-1.96 N-m (14-17 lb.-in.)

Ambient Temperature

Enclosure Rating

Minimum Mounting
Clearances

Minimum

Maximum

-10°C (14°F)

40°C (104°F)

IP 20/Open Type

Use Mounting Option A

IP 30/NEMA 1/UL Type 1

(1)

(1)

Rating requires installation of the PowerFlex 4 IP 30/NEMA 1/UL Type 1 option kit.

Use Mounting Option B

50°C (122°F) IP 20/Open Type

Use Mounting Option B

25 mm

(1.0 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

120 mm

(4.7 in.)

Mounting Option A
No clearance required
between drives.

Mounting Option B

See page 12 for mounting dimensions.

General Grounding Requirements

U/T1
V/T2

W/T3

R/L1
S/L2

T/L3

SHLD

Important: Remove the MOV to ground jumper if the
drive is installed on an ungrounded distribution system.

Tighten screw after jumper removal.

Jumper
Location

CE Conformity