The Program Group contains the most commonly used parameters.

Display Group Parameters

No.

Parameter

Min/Max

Display/Options

d001 [Output Freq]

0.0/[Maximum Freq]

0.1 Hz

d002 [Commanded Freq]

0.0/[Maximum Freq]

0.1 Hz

d003 [Output Current]

0.00/(Drive Amps × 2)

0.01 Amps

d004 [Output Voltage]

0/Drive Rated Volts

1 VAC

d005 [DC Bus Voltage]

Based on Drive Rating

1 VDC

d006 [Drive Status]

0/1 (1 = Condition True)

Bit 3

Bit 2

Bit 1

Bit 0

Decelerating

Accelerating

Forward

Running

d007-
d009

[Fault x Code]

F2/F122

F1

d010 [Process Display]

0.00/9999

0.01 – 1

d012 [Control Source]

0/9

Digit 1 = Speed Command

Digit 0 = Start Command

(See P038; 9 = “Jog Freq”)

(See P036; 9 = “Jog”)

d013 [Contrl In Status]

0/1 (1 = Input Present)

Bit 3

Bit 2

Bit 1

Bit 0

Reserved

Stop Input

Dir/Run REV

Start/Run FWD

d014 [Dig In Status]

0/1 (1 = Input Present)

Bit 3

Bit 2

Bit 1

Bit 0

Reserved

Reserved

Digital In2 Sel

Digital In1 Sel

d015 [Comm Status]

0/1 (1 = Condition True)

Bit 3

Bit 2

Bit 1

Bit 0

Fault Occurred

RS485 Option Transmitting

Receiving

d016 [Control SW Ver]

1.00/99.99

0.01

d017 [Drive Type]

1001/9999

1

d018 [Elapsed Run Time]

0/9999 Hrs

1 = 10 Hrs

d019 [Testpoint Data]

0/FFFF

1 Hex

d020 [Analog In 0-10V]

0.0/100.0%

0.1%

d021 [Analog In 4-20mA]

0.0/100.0%

0.1%

d024 [Drive Temp]

0/120 degC

1 degC

Smart Start-Up with Basic Program Group Parameters

= Stop drive before changing this parameter.

No.

Parameter

Min/Max

Display/Options

Default

P031 [Motor NP Volts]

20/Drive Rated Volts

1 VAC

Based on Drive Rating

Set to the motor nameplate rated volts.

P032 [Motor NP Hertz]

10/240 Hz

1 Hz

60 Hz

Set to the motor nameplate rated frequency.

P033 [Motor OL Current]

0.0/(Drive Rated Amps×2) 0.1 Amps

Based on Drive Rating

Set to the maximum allowable motor current.

P034 [Minimum Freq]

0.0/240.0 Hz

0.1 Hz

0.0 Hz

Sets the lowest frequency the drive will output continuously.

P035 [Maximum Freq]

0/240 Hz

1 Hz

60 Hz

Sets the highest frequency the drive will output.

P036 [Start Source]

0/5

0 = “Keypad”

(1)

1 = “3-Wire”
2 = “2-Wire”

3 = “2-W Lvl Sens”
4 = “2-W Hi Speed”
5 = “Comm Port”

0

Sets the control scheme used to start the drive.

(1)

When active, the Reverse key is also active unless disabled by A095 [Reverse Disable].

P037 [Stop Mode]

0/7

0 = “Ramp, CF”

(1)

1 = “Coast, CF”

(1)

2 = “DC Brake, CF”

(1)

3 = “DCBrkAuto,CF”

(1)

4 = “Ramp”
5 = “Coast”
6 = “DC Brake”
7 = “DC BrakeAuto”

0

Active stop mode for all stop sources [e.g. keypad,
run forward (I/O Terminal 02), run reverse (I/O
Terminal 03), RS485 port] except as noted below.
Important: I/O Terminal 01 is always a coast to stop input except when P036 [Start Source] is set for “3-Wire” control.
When in three wire control, I/O Terminal 01 is controlled by P037 [Stop Mode].

(1)

Stop input also clears active fault.

P038 [Speed Reference]

0/5

0 = “Drive Pot”
1 = “InternalFreq”
2 = “0-10V Input”

3 = “4-20mA Input”
4 = “Preset Freq”
5 = “Comm Port”

0

Sets the source of the speed reference to the
drive.
Important: When A051 or A052 [Digital Inx Sel] is set to option 2, 4, 5, 6, 13 or 14, and the digital input is active, A051
or A052 will override the speed reference commanded by this parameter. Refer to Chapter 1 of the PowerFlex 4 User
Manual
on CD for details.

P039 [Accel Time 1]

0.0/600.0 Secs

0.1 Secs

10.0 Secs

Sets the rate of accel for all speed increases.

P040 [Decel Time 1]

0.1/600.0 Secs

0.1 Secs

10.0 Secs

Sets the rate of decel for all speed decreases.

P041 [Reset To Defalts]

0/1

0 = “Idle State”
1 = “Reset Defaults”

0

Resets all parameter values to factory defaults.

See the PowerFlex 4 User Manual on CD for more information on parameters.