TROUBLESHOOTING

Tower Dryer Operations & Service

32

Problem

What to do

Dryer shuts down, red light lights

- Check for possible fire in dryer at location indicated in message.

and horn sounds, display shows:

- Check for a plugged or slow moving grain column.

“OVERHEAT AT _________”

- Check for a plugged grain turner.

“POSSIBLE FIRE”

- Check to insure that the dryer is full of grain and is continually being kept full.
- Check for a defective high limit sensor.

OIU displays message:

- Indicates that the metering system inverter drive has tripped.

“UNLOAD DRIVE FAULT”

- Check for plugged metering drum or Accutrol metering system.
- Reset drive by turning off the main circuit breaker for 15 seconds, or by pressing the
“STOP” button on the inverter.

OIU displays message:

- Indicates that any overload has occurred in the item indicated.

“CONTACT FAILED TO CLOSE” - Reset the overload of the starter indicated in the power panel and fix the
“DRY CONVEYOR”

overloaded conditions.

-or-
“WET CONVEYOR”
-or-
any auxiliary starter

OIU displays message:

- Indicates that overload has occurred in the blower indicated.

“OVERLOAD TRIPPED”

- Reset the overload of the starter of the blower indicated and fix the

“BLOWER __ STARTER”

overload conditions.
- Blower overload can be caused by overly tightened blower belts or inadequately greased
blower bearings.

TROUBLESHOOTING – OIU (SCREEN) MESSAGES

Message

What to do

LOST COMM. TO MICRO

Cycle the power

OVERHEAT AT TOP LEFT POSSIBLE FIRE!!!

Check overheat condition and Term. 101

OVERHEAT AT TOP RIGHT POSSIBLE FIRE!!!

Check overheat condition and Term. 102

OVERHEAT AT MID. LEFT POSSIBLE FIRE!!!

Check overheat condition and Term. 103

OVERHEAT AT MID. RIGHT POSSIBLE FIRE!!!

Check overheat condition and Term. 104

OVERHEAT AT LOWER LEFT POSSIBLE FIRE!!!

Check overheat condition and Term. 105

OVERHEAT AT LOWER RIGHT POSSIBLE FIRE!!!

Check overheat condition and Term. 106

OVERHEAT AT INSIDE LEFT POSSIBLE FIRE!!!

Check overheat condition and Term. 107

OVERHEAT AT INSIDE RIGHT POSSIBLE FIRE!!!

Check overheat condition and Term. 108

OVERHEAT AT PLENUM POSSIBLE FIRE!!!

Check overheat condition and Term. 109

OVERLOAD TRIPPED TRI-STARTER

Check Term. 300

OVERLOAD TRIPPED BLOWER 1 STARTER

Check Term. 301

OVERLOAD TRIPPED BLOWER 2 STARTER

Check Term. 302

OVERLOAD TRIPPED BLOWER 3 STARTER

Check Term. 303

OVERLOAD TRIPPED BLOWER 4 STARTER

Check Term. 304

AUXILIARY STUCK CLOSED TRI-STARTER

Check Term. 200

AUXILIARY STUCK CLOSED BLOWER 1 STARTER

Check Term. 201

AUXILIARY STUCK CLOSED BLOWER 2 STARTER

Check Term. 202