PAGE 18

Residential Water Systems

CentriPro

motor rating

75º C Insulation - awG Copper wire Size

Volts hp 14 12 10 8 6 4 2 1 1/0 2/0 3/0 4/0 250 350 500

230V 5 0 100 170 260 430 680 1060 1330 1660 2070 2560 3190

60 Hz. 7.5 0 0 120 200 310 490 760 940 1150 1420 1740 2120

Single

10 0 0 0

140 220 340 520 660 810 1020 1250 1540

Phase

15 0 0 0 0

140 230 370 450 560 700 870 1080

5 140 230 370 590 920 1430 2190 2690 3290 4030 4850 5870 6650 8460

230V 7.5 0 150 250 410 640 1010 1540 1900 2310 2840 3400 4120 4660 5910 7440
60 Hz. 10 0 0 180 300 470 740 1140 1410 1720 2110 2550 3090 3510 4500 5710

Three

15 0 0 0

200 320 510 790 970 1180 1450 1760 2120 2410 3080 3900

Phase

20 0 0 0

150 240 390 600 750 920 1130 1370 1670 1900 2440 3100

3 Lead

25 0 0 0 0

190 310 490 600 730 900 1100 1330 1510 1950 2480

30 0 0 0 0 0

250 390 490 590 730 890 1080 1230 1580 2030

5

590

950

1500

2360

3700

5750

7.5

410

670

1060

1670

2610

4060

6200

7610

10

300

480

770

1220

1910

2980

4580

5630

6900

15 0 330 530 840 1320 2070 3160 3890 4760 5840 7040

20

0

0

400 640 1020 1600 2460 3020 3710 4560 5500

460V 25 0 0 320 520 810 1280 1960 2410 2960 3640 4400 5350

60 Hz.

30 0 0 0

410 650 1030 1570 1950 2390 2940 3560 4330 4940

Three

40 0 0 0

320 500 790 1220 1500 1840 2270 2730 3320 3760

Phase

50 0 0 0 0

390 610 940 1170 1430 1750 2110 2560 2910 3700 4690

3 Lead

60 0 0 0 0 0

540 830 1020 1250 1540 1860 2250 2550 3260 4120

75 0 0 0 0 0

430 660 820 1000 1230 1480 1810 2050 2640 3360

100

0 0 0 0 0 0

490 610 750 930 1120 1360 1540 1990 2520

125

0 0 0 0 0 0 0 0

620 770 920 1040 1270 1620 2040

150

0 0 0 0 0 0 0 0 0

620 750 910 1040 1330 1680

200

0 0 0 0 0 0 0 0 0 0

610 740 840 1070 1370

Lengths IN bolD typE meet the National Electric Code ampacity only for individual conductor 75º C cable, in free air or water. If other cable
is used, the National Electric Code as well as the local codes should be observed.

NotE: Since 60º C cable is no longer the industry standard and is not readily available, we have removed the chart.