PAGE 40
Residential Water Systems
CentriPro
traNSformEr SIzES
A full three phase supply is recommended for all three
phase motors, consisting of three individual trans-
formers or one three phase transformer. “Open” delta
or wye connections using only two transformers can
be used, but are more likely to cause problems from
current unbalance.
Transformer ratings should be no smaller than listed in
the table for supply power to the motor alone.
traNSformEr CapaCIty rEquIrED for Sub-
mErSIblE motorS
Smallest kVa rating –
Submersible total Effective
Each transformer
3Ø motor
kVa
open wyE
wyE or
hp rating
required
DElta 2
DElta 3
transformers transformers
1½ 3 2 1
2 4 2 1½
3 5 3 2
5 7½ 5 3
7½ 10 7½ 5
10 15 10 5
15 20 15 7½
20 25 15 10
25 30 20 10
30 40 25 15
40 50 30 20
50 60 35 20
60 75 40 25
75 90 50 30
100
120
65
40
full thrEE phaSE
opEN DElta or wyE