3 phaSE StartEr VoltaGE ChECkout
Checking Voltage at fused Disconnect and
magnetic Starter
powEr IS oN during voltage
checking.
1. To check voltage: Use voltmeter on L1, L2 and L3 in
sequence. Check should be made at four locations.
Step 1 Checking incoming power supply.
Step 2 Checking fuses.
Step 3 Checking contact points
Step 4 Checking heaters.
2. When checking voltage, all other major electrical
appliances (that could be in use at the same time)
should be running.
3. If incoming power supply readings are not within
the limits (see chart), call your power supplier.
Voltage limits
Name plate
measured Volts
▼
minimum maximum
208V 3Ø
188
228
230V 3Ø
207
253
460V 3Ø
414
506
575V 3Ø
518
632
NotE: Phase to phase – full line voltage. Phase to
neutral – ½ full line voltage. (depending on
transformer connection)
WARNING
VOLT
600-
500-
400-
300-
200-
100-
0-
RULE OF THUMB
Incoming power should be within 5% of power
supply voltage. Motors are rated ±10% of
nameplate. The other 5% is used for cable voltage
drop.