CSCr 1Ø CoNtrol boXES CapaCItor Start - CapaCItor ruN

for uSE wIth 3 wIrE, 1Ø, 4" CENtrIpro motorS aND 4" (6", 5 hp) fraNklIN ElECtrIC motorS

Control box

may

may replace

may replace

Standard

Standard

Dual Element Enclosure

Shipping

order

hp kw Volts replace

rJ #

fE #

Circuit

fuse

time Delay Dimensions

wt. (lbs)

Number

Gp #

breaker

fuse

w x D x h (in)

CB05412CR 0.5 .37 230

①

50F311CB

2824055015①

10

15

10

8.1 x 5.9 x 9.3

7

S50N1CB, A50N1CB

CB07412CR .75 .55 230

①

75F311CB

2824075015①

15

20

10

8.1 x 5.9 x 9.3

7

S75N1CB, A75N1CB

CB10412CR 1 .75 230

①

S100F311CB

2824085015①

15

20

10

8.1 x 5.9 x 9.3

7

S100N1CB, A100N1CB

CB15412CR 1.5 1.1 230 00074

150F311CB

282 3008 110

25

30

15

8.1 x 5.9 x 9.3

7

S150N1CB, A150N1CB

CB20412CR 2 1.5 230 00084

200F311CB

282 3018 110

25

30

20

8.1 x 5.9 x 9.3

7

S200N1CB, AS200T1CB

CB30412CR 3 2.2 230 00094

300F311CB

282 3028 110

40

45

25

8.1 x 5.9 x 9.3

7

S300N1CB

CB50412CR 5 3.7 230 00104

500F311CB

282 1138 110

60

80

45

8.1 x 5.9 x 9.3

8

S500N1CB

“k” rEpaIr partS

Control box

old Control

Capacitor

Capacitor Capacitor Capacitor Capacitor

overload

Start relay

order

hp Volts box order repair part

mfd.

type

Voltage ③ quantity order order

Number

Number

Number

Number

②

Number

CB05412CR .5 230

①

9K465 43-53 Start 250

1 NA 9K458

9K466

15

Run 370

CB07412CR .75 230

①

9K448 59-71 Start 250

1 N/A 9K458

9K467

23

Run 370

CB10412CR 1 230

①

9K449 86-103 Start 250

1 N/A 9K458

9K467

23

Run 370

CB15412CR 1.5 230

00074

9K447 105-126 Start 250

1 9K471 9K458

9K466

15

Run 370

CB20412CR 2 230 00084

9K447 105-126 Start 250

1 9K481 9K458

9K451

20

Run 370

CB30412CR 3 230 00094

9K453 208-250 Start 250

1 9K482

9K454

45

Run 370

9K459

CB50412CR 5 230 00104

9K455 270-324 Start 330

1

9K483

9K456

40

Run 370

2

①

New ½ – 1 HP CSCR control box is now in a larger enclosure, it is not in a quick disconnect style enclosure.

②

Overloads for 2, 3 and 5 HP CSCR boxes are sold prewired and soldered as an assembly. No field soldering or wiring required.

③

It is allowable to substitute capacitors with higher voltage ratings but never lower ratings. Mfd. ratings are mandatory.

Order Number 9K479 for 200/208 Volt Start Relay.