Installation procedures, Electrical connections continued – Xylem IM098 AQUAVAR Model 56 Controller User Manual

Page 14

Advertising
background image

5) Input Power Cable Installation: The main

power cable is connected to GRD #2, L1, L2
for 230 Volt single phase.
• Route the cable through the strain relief per

diagram #7, cut to length and connect.

• See Appendix B for protection requirements.

6) For Multi-Pump Systems: Use a three core

shielded cable to connect terminals X3/1,
X3/2 and X3/3 between the AQUAVAR Model 56
Controller units. These are the RS-485 interface
connections. (See diagram 6 and 8). Shielding
may be grounded on terminal X3/3.

7) Low Water Switch: Used to indicate low

water, connect to terminals X2/6 and X2/7.
Refer to diagram 6.

Jump terminals if not used.

8) External On/Off: Used to turn the AQUAVAR

Model 56 Controller on/off from an external panel
or controller, connect to X2/5 and X2/4. Refer
to diagram 6.

Jump terminals if not used.

9) Relay: This connection may be used to turn

on/off a full speed slave pump or an external
run or error indicator. Wire the relay to the
switch controlling the device selected.
(X2/10, X2/11, and X2/12)

Installation Procedures

9

Electrical Connections continued

AV 1.1

AV 1.15, 1.2

Motor

connections

Control

terminals

Terminals of

the RS485

interface

Main supply

connections

Motor

connections