Pump Priming

Refer to your pump operation manual for instructions on pump priming.

Run Test

WARNING

DO NOT APPLY POWER TO THE AQUAVAR MODEL 56 CONTROLLER OR PUMP UNTIL
ELECTRICAL CONNECTIONS HAVE BEEN REVIEWED BY A QUALIFIED ELECTRICIAN AND MEET
ALL APPLICABLE STATE AND LOCAL REQUIREMENTS.

Instructions

1) Check all wiring. All motors used with the

AQUAVAR Model 56 Controller are three
phase TEFC (a wall mounted version permits
the use of other enclosures). You will need to
check the direction of rotation of the motor
shaft. If you have followed all of the previous
steps carefully, you should now be ready to
apply power to the AQUAVAR Model 56
Controller unit.

2) Close discharge valve. Make sure the

discharge valve is closed. Apply power to the
AQUAVAR Model 56 Controller.

3) The next step is to apply power to the AQUAVAR

Model 56 Controller and check for proper rotation
of the motor. The first start up of the AQUAVAR
Model 56 Controller should be done with the
external programming device. If you operate the
AQUAVAR Model 56 Controller without the
programming device, the following parameters
have to be set in the submenu (see operation in
the main menu).
◆ Change pressure: ENABLED
◆ Autostart: ENABLED

The AQUAVAR Model 56 Controller is
delivered with these settings as standard.

Change Pressure without Remote Control

1) Start the pump with the push button on

the front plate of the AQUAVAR Model 56
Controller.

2) Then press the and buttons together

for more than 3 seconds.

Installation Procedures

10

NO AUTOSTART – DISABLE INVERTER

Screen