Operator Custom Features and Displays

Ramp Hysteresis Level Where the fast
ramp changes to the slow ramp. Possible
setting: between 0% – 100% of the window.

Fast Acceleration Time Time setting at
Ramp 1, 2, 3, or 4 will influence the control of the
pump and MUST NOT BE CHANGED for
normal operation. Possible setting for each
ramp 0,05 – 1000 sec. Excessively fast running
time may overload the inverter. Excessively
slow running up time may cause a break down
of the outgoing pressure.

Fast Deceleration Time Excessively fast
running down time tends to cause oscillation
or hunting or can cause an error
(OVERVOLTAGE) during slow down of the
pump. Excessively slow running down time
tends to generate over pressure.

Slow Acceleration Time Too slow of a
running up time during variation of demand can
cause the outgoing pressure to break. Too
fast of a running up time may lead to over
oscillation and/or overload of the inverter.

Slow Deceleration Time Too fast a setting leads
to oscillation. Too slow a setting delays switching
off too much.

Ramp Window

30

HYSTERISIS

80%

ACCEL. HIGH

4 SEC.

DECEL. HIGH

4 SEC.

ACCEL. LOW

70 SEC.

DECEL. LOW

70 SEC.

PRESSURE

R1

R3

R4

R1

R3

R2

R4

R3

R4

SET HYSTERESIS %

SET HYSTERESIS %

100%

SET RATED
PRESSURE

WINDOW
SETTING IN % OF
RATED PRESSURE

R1: SPEED RAMP FAST INCREASE
R2: SPEED RAMP FAST DECREASE
R3: SPEED RAMP SLOW INCREASE
R4: SPEED RAMP SLOW DECREASE

Diagram 10