Operator Custom Features and Displays

Submenu Sensor To enter this menu you
have to press the key, to leave the menu,
press the ➔ key longer than 3 seconds.

Sensor – Adjust (Zero adjustment of the
transmitter) Depressurize the system and press
keys + simultaneously. After adjustment
“adjusted” appears on the display. If “out of
range” is shown on the display, no adjustment
is possible.

Sensor Max-Adjust The analogue input
(terminal X2/2) is prepared for a transmitter
signal of 0,5 - 4,5VDC (= 100%). When there is
a transmitter with another signal range used,
you have to adjust this other voltage range in
this parameter.

To leave the submenu press the ➔ key longer than 3 seconds.

Submenu Test-Run To enter this menu you
have to press the key, to leave the menu,
press the ➔ key longer than 3 seconds.

Start Test Run By simultaneously
pressing + a test run will be released even
if the test cycle is not set.

Sequence for Automatic Test Run
Adjustable between 10 – 100 hours. The test run
starts the pump for 20 seconds at 30 Hz at
the set time after the last stop. Deactivating test
run: Set 0 hours, by using and .
Repeating the test run: Select test run and set
the desired hours using the key .

Test Run: Frequency Frequency for
manual test run can be set from 0 Hz to 60 Hz.

Test Run: Boost Start voltage in % of
rated voltage in order to ensure that the motor
starts safely. Adjustable between 0% and 25%.

To leave the submenu press the ➔ key longer than 3 seconds.

34

SUBMENU

SENSOR

SENSOR – ADJUST?

OUT OF RANGE

SUBMENU

TESTRUN

START TEST RUN

+

TIME TEST RUN

100 h

TEST FREQUENCY

60 Hz

SENSORMAX – ADJUST

100%

BOOST TEST RUN

5.0%