Error signals, Operator custom features and displays – Xylem IM098 AQUAVAR Model 56 Controller User Manual

Page 42

Advertising
background image

Controller Menu Address To enter this menu
you have to press the key, to leave the menu,
press the ➔ key longer than 3 seconds.

Change of Pump Address Addresses
from 01 to 04 and also 00 can be set in this
parameter. To change the address it is
necessary to cut the interface connection to
other AQUAVAR Model 56 Controllers. The address
of the AQUAVAR Model 56 Controller is shown on
the left side. On the right side, you can give the
AQUAVAR Model 56 Controller a new address
with the buttons and . You only can give an
address, which is not used in the pump group. To
change between left and right side, press button ➔
or . The star shows the actual side used. If you
select address 00, this setting will be accepted
after release of the button.

To leave the submenu press the ➔ key for 3 seconds.

Error Signals

Low Water Remedy: Check suction pressure
If suction pressure is normal the unit restarts
itself. If there is no suction pressure switch
(e.g. circulating systems), bridge terminals
X2/6 and X2/7. (Jumper wire if not used.)

Overheating – Motor Possible causes:
Insufficient cooling ambient temperature is too
high, motor overloaded. After the cause has
been remedied, the malfunction has to be reset
by cutting off the power supply for > 30 seconds.

Overvoltage Possible cause: Check main
supply, supply voltage too high, peak voltage due
to switching heavy loads on the network,
or RAMP 2 is too fast. Find the cause and take
countermeasures (e.g. line filter, RC-elements).
Disconnect the power supply for > 30 seconds.

Operator Custom Features and Displays

37

SUBMENU

ADDRESS

ADDRESS CHANGE

00 ➔ 00 *

XXX

ERROR WATER

XXX

ERROR – MOT – TEMP

XXX

ERROR – OVERVOLT