Xylem IM098 AQUAVAR Model 56 Controller User Manual
Page 45
40
Appendix A (continued)
Differential Pressure Transducer
The sensors of this differential pressure transducer are two piezoresistive silicon pressure sensors,
mounted on a tape (TAP) freely floating in an oil chamber. The pressure is transferred to the sensor by a
separate steel diaphragm in the oil chamber.
Specifications
Range (FS):
4 bar (differential)
Over-pressure-Pmax:
16 bar (single-sided)
Class of protection:
IP 65
Type
Sealed gauge:
Signal Output:
0,5 - 4,5 V DC (ratiometric)
Supply:
5 VDC +/- 10%
Load Resistance:
≥ 5 kΩ
Linearity:
± 0.20 % FS; max. ± 0.5% FS
Stability:
± 0.1 % FS; max. ± 0.2% FS
Operating Temperature:
-10 - +80°C
Storage Temperature:
-40 - +100°C
Material:
Body and diaphragm: 1.4435 Stainless Steel
Screw Joint and Cover:
60 26
44
≈ 95
40
PLUG: mPm 193
INCL. 2m CABLE
Out (white)
+ Vcc (brown)
GND (green)
Screen