Xylem IM098 AQUAVAR Model 56 Controller User Manual

Page 45

Advertising
background image

40

Appendix A (continued)

Differential Pressure Transducer

The sensors of this differential pressure transducer are two piezoresistive silicon pressure sensors,
mounted on a tape (TAP) freely floating in an oil chamber. The pressure is transferred to the sensor by a
separate steel diaphragm in the oil chamber.

Specifications
Range (FS):

4 bar (differential)

Over-pressure-Pmax:

16 bar (single-sided)

Class of protection:

IP 65

Type

Sealed gauge:

Signal Output:

0,5 - 4,5 V DC (ratiometric)

Supply:

5 VDC +/- 10%

Load Resistance:

≥ 5 kΩ

Linearity:

± 0.20 % FS; max. ± 0.5% FS

Stability:

± 0.1 % FS; max. ± 0.2% FS

Operating Temperature:

-10 - +80°C

Storage Temperature:

-40 - +100°C

Material:

Body and diaphragm: 1.4435 Stainless Steel

Screw Joint and Cover:

60 26

44

≈ 95

40

PLUG: mPm 193

INCL. 2m CABLE

Out (white)

+ Vcc (brown)

GND (green)

Screen