Programming – Xylem IM098 AQUAVAR Model 56 Controller User Manual

Page 19

Advertising
background image

To set run out protection:

Note

Run out protection occurs if the pump is running at full speed, and the set pressure cannot be
recorded after a set period of time. To set run out protection you need to enter the amount of
pressure drop and the time delay.

Instructions
1) Password The password protection prevents

untrained personnel from accidentally changing
the base setting.
• From the parameter screen on the main menu
press the arrow until the display changes to:

2) Press the arrow until you reach the number

0066.

3) Press the ➔ arrow repeatedly until you reach:

4) Press the arrow once and you will reach:

5) By pressing the arrow. Enter the pressure

setting (in psi) at which you want the pump to
shutoff. Typically a setting of 3 to 5 psi less
than the standard pressure setting would be
entered.

6) Now press the ➔ arrow and you will reach:

7) By pressing the arrow you will be entering

the amount of time (in seconds) that the pump
will run at the pressure setting programmed
into the conveyor limit before it automatically
shuts off. Returning to normal operation:

8) Hold the ➔ arrow down for 3 seconds and you

will be returned to:

9) Hold the ➔ arrow down again for 3 seconds

and you will be returned to: The Main Menu.

Programming

14

CONVEYOR LIMIT

0.0 PSI

CONVEYOR LIMIT

25 PSI

ERROR DELAY

0S

ERROR DELAY

5S

SUBMENU

ERROR

PASSWORD

0000

PASSWORD

0066

SUBMENU

ERROR

PRESSURE 00 PSI

SPEED 00HZ

Advertising