Xylem IM098 AQUAVAR Model 56 Controller User Manual
Page 2
AQUAVAR Model 56 Controller Owner’s Information Record
Aquavar Model 56 Controller
Pump Code Number
S/N
Transducer Model
Date Purchased
Transducer Rating
Purchased From
Program Record
Parameter
Range (Default)
User Setting
Actual Pressure
N/A
Read-Only
Set Pressure
0-150 psi (45 psi)
Submenu Parameter
N/A
Read-Only
Password
(66)
Read-Only
Submenu Diagnostics
N/A
Read-Only
Motor Hours
N/A
Read-Only
S10 Address
N/A
Read-Only
Error
N/A
Read-Ony
Overload Error
N/A
Read-Only
OverVolt Error
N/A
Read-Only
Software Version
N/A
Read-Only
Change Pressure
Disable (Enable)
Autostart
Disable (Enable)
Mode
Actuator, (Controller), Multicontroller
Regulation Mode
(Normal), Inverse
Dimension Unit
(psi), bar, %
Submenu Inverter
N/A
Read-Only
Maximum Frequency
6-60 Hz (60 hz)
Minimum Frequency
0-60 Hz (0 Hz)
Boost
0-25% (5%)
Configuration –
Minimum Frequency
Fmin (F = 0)
Submenu Control
N/A
Read-Only
Window
0-100% (15%)
Hysterisis
0-100% (80%)
Acceleration High
1.0-999.9 (4 sec.)
Deceleration High
1.0-999.9 (4 sec.)
Acceleration Low
1.0-999.9 (70 sec.)
Deceleration Low
1.0-999.9 (70 sec.)
Lift Frequency
6-60 Hz (30 Hz)
Lift Intensity
0-100% (0%)