AQUAVAR Model 56 Controller Drive Head Technical Data

AQUAVAR Model 56

Supply

Motor

Voltage

Controller

Protection

Type

Rated output

Voltage

AV 1.1

1 HP

1 x 230 V / 40-60 Hz

3 x 230 V

4,8 A

10 Ampere

AV 1.15

2 HP

1 x 230 V / 40-60 Hz

3 x 230 V

7,0 A

10 Ampere

AV 1.2

3 HP

1 x 230 V / 40-60 Hz

3 x 230 V

10,0 A

16 Ampere

Input Voltage:

1 x 230 VAC ± 10% (An input line reactor is highly recommended
for areas which experience voltage fluctuation.)

Output Voltage:

3 x 230 Volt AC

Max. Frequency:

40 – 60 Hz – selectable

Min. Frequency:

0 - f-max

Electrical Efficiency:

> 95%

Protection against:

Short circuit, under-voltage, overheating of the electronics (overload) and
additional protective functions via external switch (motor temperature,
low water).

A power supply filter is included to ensure interference immunity.

The AV Series frequency converter complies with the general EMV provisions and has been tested according
to the following standards:

• Radio Interference Suppression EN 50081 Part 2 and EN 50082 Part 2
• High Frequency Field Interference ENV 50140 and ENV 50141
• Static Electricity Discharge EN 61000-4
• Disturbance Voltage EN55011

Ambient Temperature:

5° C – 40° C

Storage Temperature:

-25° C – +55° C
(+70° C during max. 24 hours)

Humidity:

rH max. 50% at 40° C, unlimited
RH max. 90% at 20° C, max. 30 days per year
Condensation not permitted!

Air Pollution:

The air may contain dry dust as found in workshops where there is no
excessive quantity of dust due to machines. Excessive amounts of dust,
acids, corrosive gases, salts, etc. are not permitted.

Class of Protection:

UL, CUL, NEMA 4, IP 55

Altitude:

Maximum 3000 feet above sea level. Consult factory for higher altitudes.

41