Operator custom features and displays – Xylem IM098 AQUAVAR Model 56 Controller User Manual

Page 40

Advertising
background image

Submenu Error The inverter tries to reach a
defined pressure limit in a defined time. If this is not
possible the inverter stops. To enter this
menu you have to press the key, to leave
the menu, press the ➔ key longer than 3
seconds.

Conveyor Limit Disabled or adjustable
between 0.00 and 100%. To disable the
conveyor limit, press till “0.0%” is shown
on the display. To set a % pressure the
or .

Error Delay Adjustable between 0 and
100 sec. Delayed switch-off in the event of low
water, (suction side switch connected to
terminal X2/6-X2/7) and also for the conveyor limit.
Time Setting.

To leave the submenu press the ➔ key for longer than 3 seconds.

Set Password The pre-set password can be
changed if necessary with the and keys.

Default Settings To load DEFAULT –
PARAMETER, press buttons + together,
until the timer is run down.

Submenu Diagnosis To enter this menu you
have to press the key, to leave the menu,
press the ➔ key longer than 3 seconds.

Pump Runtime Shows the run time of
the pump.

Pump Address This window shows the
adjustment of the pump address, Read Only.

* The last three error signals are always stored with Signal Error 1 to 3.

* The error signals can not be deleted.

* The signal ERROR 1 shows the last error to have occurred.

Operator Custom Features and Displays

35

SUBMENU

ERROR

CONVEYOR LIMIT

0.0%

ERROR DELAY

2 SEC.

SET PASSWORD

0066

DEFAULT

+

SUBMENU

DIAGNOSIS

PUMP RUNTIME

0000 STD.

PUMP-ADDRESS

1