Xylem IM182 Balanced Flow User Manual

Page 10

Advertising
background image

10

4: TROUBLESHOOTING

The status light described in Section 3 Installer Pre-Start Selections is used to indicate system status i.e. running,

stopped, or faulted. When faulted, the status light will be red. The error code is the number of quick flashes followed

by a 1 second pause. The number of flashes can be any number from 2 to 8. The error code will be repeated until

cleared. Some errors will clear themselves with time. Others must be cleared manually by turning the power off for 1

minute. The following table describes the various errors that can occur.

4: TROUBLESHOOTING

Table 6: Fault Blink Codes

(continued on next page)

NO LIGHT

Flashes

Controller Status

Description

None

Low/No Input Voltage

Check the input voltage to the controller. Measure the voltage between

L1 and L2 using an AC Voltmeter. This voltage should be greater

than 190Vac.

GREEN LIGHT CODES

Flashes

Controller Status

Description

Constant

Standby/Low Voltage

Constant Green Light indicates the pump is off. The system is in Standby

mode when there is no flow in the system and the pressure setting has been

reached. The system is in a Low Voltage condition when the line input

voltage drops below 190VAC.

Blinking

Pump Running

Flashing Green Light indicates the pump is running.

RED LIGHT CODES

Flashes

Controller Status

Fault Description

This information is to be used by professional installers or qualified

Controller Action

personnel only.

Constant

Controller Error

Internal controller fault. Replace controller.


2 Blinks

Dry Well

This fault can be caused by:

• Water supply level in well falls below suction inlet of pump.

• Plugged suction screen.

• Restriction in pipe between pump and pressure sensor.

• Air bound pump – see “Purging System”

• Incorrect setting of “MAXIMUM SPEED” switch. Be sure to set the

“MAXIMUM SPEED” switch to 80 Hz when using mismatched pumps

(water ends) and motors.

• Incorrect setting of “MOTOR OVERLOAD SETTING (SFA)” switch.

Ensure the Motor Overload Setting (SFA) Switch is not set higher than the

Service Factor Amps (SFA) listed on the motor nameplate.

In systems where the motor operates at less than Service Factor Amps the

controller may show a false “dry well” fault. See Dry Well Sensitivity Section.

If problems persists, please verify supply capacity.

The controller will automatically restart according to the chart below.

Dry Well Fault Reset table:

Fault 1 (Start Point) - resets after 1 minute

Fault 2 - resets after 10 minutes

Fault 3 - resets after 20 minutes

Fault 4 - resets after 30 minutes

Fault 5 - resets after 60 minutes

Will repeat every 60 minutes, when the system cycles Off the

Dry Well will default back to the start point.

To clear the fault, turn off

power to the controller, wait

1 minute, turn on power to

the controller. If fault persists

contact installer.

The controller will

automatically restart according

to the table shown on the right.

If fault persists contact installer.

Advertising