Ratings, Required materials, Installation – Xylem IM182 Balanced Flow User Manual

Page 4: Controller, Opening controller cover, Mounting controller, Pump and piping, Table 1: tank sizing selection, For a 5 psi pressure drop set-up, For a 20 psi pressure drop set-up

Advertising
background image

4

Ratings

Refer to serial number label on enclosure.

Required Materials

• BF Pump Controller with Transducer and Transducer Wire
• Pump (water end)

(see Speed Selector Switch for 60 Hz or 80 Hz Operation)
• Motor: 230 V, three phase (3Ø), 3450 RPM
• Pressure Relief Valve – piped to a drain for safety
• Pressure Gauge – for setting system pressure
• Heat Shrink Kit – one required for each underwater or

underground splice (mandatory)

• Tank Tee or (2) ¼" NPT Female pipe fittings for pressure

sensor and pressure gauge connections

• Pipe and fittings – as necessary per each system
• Disconnect Switch: 230 V, 2 pole, properly sized

(see Controller, Breaker, Generator Sizing Table)

• Copper Wire: Minimum 75ºC rated wire, double

jacketed is recommended but not mandatory

(see Wire Sizing table)

• Tank: diaphragm style tank

(see Tank Sizing Section and Chart)

2: INSTALLATION

Determine where the Controller, Pressure Tank and

Transducer will be located before starting the installation.

Controller

The controller is rated NEMA 3R (Raintight) so it may be

located outdoors. It must be mounted vertically. Locate

the enclosure in a shaded area where the temperature

stays within 0ºF to +122ºF (-18ºC to +50ºC). Since the

controller is designed for outdoor mounting it may be

located at the wellhead.

Opening Controller Cover

Lay the controller on a flat surface or hang

on wall before removing the cover screw.

Failure to do so may result in dropping and damaging the

unit. Once screw is removed, lift the cover up and out to

remove. There is a locking tab on the bottom of the unit to

accommodate a padlock if so desired.

Mounting Controller

Three screws are provided for mounting the enclosure.
Using the enclosure as a guide, select a mounting location.

First install the top screw in the mounting surface leaving

the head of the screw approximately

1

8

" from the surface.

Hang the enclosure on this screw. Finish by installing the

two bottom screws and tightening the top screw. Be sure

to leave a minimum of 6" of clearance on each side of the

controller to ensure proper cooling.

Pump and Piping

Do not install any valves, flow control

devices or filters between the pressure

transducer and the pump. It is allowable to run branches

off the pipe between the pump and transducer as long

as no flow restricting devices are between the pump and

transducer.
NOTICE: The terms Transducer and Pressure Sensor are

equal and interchangeable.

2: INSTALLATION

EXPLODING TANK CAN INJURE OR

KILL.

Always protect the tank from over pressure by installing

a pressure relief valve large enough to limit the system

pressure below the maximum working pressure of the tank.

Install the tank at a point in the system where the maximum

possible system pressure cannot exceed the maximum

working pressure of the tank. Install the pressure relief valve

at the tank.

Avoid property damage caused by pressure

relief valve opening. Pipe the pressure relief

valve discharge to a drain or other location so that property

damage and flooding will not occur.

Locate the tank and transducer where they

will not freeze.

Ensure the system pressure setting does not exceed the

maximum working pressure of the tank.
For optimum performance, as a minimum, we recommend

using the same size pipe as the pump discharge between the

pump and the tank. Smaller diameter pipe may severely limit

the maximum capacity of the system. On long runs, larger

pipe may be beneficial for optimum performance and flow.

If using a torque arrestor, install it on the

discharge pipe before connecting pipe to

the discharge head.

Diaphragm Tank Sizing and Pre-Set Pressure

Recommendations:
Diaphragm type (captive air) tanks are required on these

systems.

Table 1: Tank Sizing Selection

Maximum

Recommended Tanks

Pump GPM

Total Volume

Order No. or

Order No.

10

2

V6P

TP6P

23

4.5

V15P

TP15P

41

8.2

V25P

TP25P

70

13.9

V45

TP45

100

19.9

V60

TP60

Use Total Tank Volume, not drawdown volume, to select

the proper tank size. The total tank volume should be

approximately 20% of the pump’s maximum flow. For

example, when using a 10 gpm pump the system requires a

2 gallon (total volume) tank.
The tank sizing recommendations are field proven to

prevent objectionable pressure drops on start-up and

provide smooth operation for the majority of variable speed

pump systems.

For a 5 PSI Pressure Drop Set-up:

Set the tank pressure, while tank is empty of water, to 20 psi

below the desired system pressure setting. Ex. for a 50 psi

system pressure, charge the tank to 30 psi.

For a 20 PSI Pressure Drop Set-up:

Start with the tank pre-charge set 30 psi below the set

point, this setting may need minor adjustment for optimum

performance as all systems and piping are slightly different.

Splicing Drop Cable To Motor Leads

The underwater connection where the drop cable connects

to the motor wires must be done using a waterproof heat

shrink kit. To make the connection, first strip the wires

½" and place the heat shrink tubes over the wires. Then,

WARNING

CAUTION

CAUTION

CAUTION

WARNING

CAUTION

Advertising