Xylem IM182 Balanced Flow User Manual

Page 5

Advertising
background image

5

CAUTION

connect the wires using the crimps. Finish by shrinking the

tubes over the crimps heating from the center outward.

The sealant in the tube will flow out the ends making a

watertight seal. If a heat shrink tube is burnt or split, the

connection will need to be remade.

Vinyl electrical tape is not acceptable for

underwater splices when using variable

speed drives due to the high potential for leakage to ground

through taped joints. Failure to use a waterproof heat shrink

kit will void the warranty.
Before installing the motor in the well, the drop cable must be

connected to the motor wires. Refer to the wire size chart when

selecting wire size for the drop cable. See Wire Sizing Table.

Wiring Pressure Transducer

Transducer wires must never be in same

conduit with power wires. There should

always be a minimum of 12" between transducer wires

and power wires. Failure to separate these wires can cause

controller malfunctions.
The pressure transducer cable is pre-wired at the factory. If

desired, the length of the cable can be changed. The cable

can also be put in conduit to protect against damage.
To change the length of the transducer cable:
• Cable length cannot exceed 200'.
• Disconnect transducer wires from terminal block by pushing

down on tabs at rear of block one at a time and pulling the

wires out of the terminal.

• Splice additional cable to transducer wire, cut off excess as

required.

• Reconnect wires to terminal block. Be sure wire colors match

labels on circuit board (B = Black, R = Red, W = White).

To put the transducer cable in conduit, do the following:

Disconnect the cable from the terminal block and remove

the cable strain relief in the bottom of the enclosure.

Starting at the enclosure, run flexible or rigid ½" conduit to

where the transducer is located. The last few feet of conduit

adjacent to the transducer will need to be flexible. The

conduit must be well supported – NO stress can be placed

on the pressure transducer connector. Use a strain relief

bushing to seal around the pressure transducer connector.

After reconnecting the transducer wires to

the terminal block and ground terminal, tug

on each wire individually to ensure they are tight.

Any exposed metal in the system piping,

including transducer case, must be grounded

to the service entrance per NFPA 70: National Electrical

Code, Article 250.
The transducer cable has a Green ground wire and a ground

clamp supplied to facilitate grounding the transducer. See

Figure 1.

Motor Wires – See Table 4

NOTE: A MINIMUM OF 75ºC COPPER WIRE IS MANDATORY.
Refer to the Table 4 for wire sizing and maximum wire

lengths. Charts are designed to limit voltage drop to 5%.

Size wire for worst case scenarios (low voltage) and stay

within the charts recommendations. Insure that the wire is

rated for direct burial and/or submergence.

Figure 1: Transducer Grounding

Figure 2 shows the terminal block where the motor and

input wires connect. The protective cover on the terminal

block snaps off and on. Attach the motor wires to the

terminals according to colors marked on circuit board:

GND = Green, RED = Red, BLK = Black, YEL = Yellow.

Reversing any two leads on RED/BLK/YEL will change the

direction of motor rotation. Later during start-up you may

need to change motor rotation.

Input Power

SHOCK OR ELECTROCUTION

HAZARD

Connect a ground wire from the service panel to the

terminal marked GND. Controller has high leakage to

ground. Controller ground terminal must be connected to

the service entrance ground terminal. Failure to do so will

result in high voltage being present on the controller chassis.

Connect two “hot” wires from the 2 pole circuit breaker to

the terminals marked L1 and L2.
The input power system used must be a grounded power

system. The voltage measured from L1 to L2 must be in the

range of 196Vac to 265Vac. The voltage measured from

L1 to GND must be equal to the voltage measured from

L2 to GND. These voltages must be within the range of

120Vac +/- 10%. Reduced input voltage will reduce system

performance.
Do not use a Ground Fault Circuit Interruptor (GFCI) with

this product or nuisance tripping will result.

Figure 2: Wiring Connections

NOTE: IT MAY BE NECESSARY TO PLACE A DISCON-

NECT SWITCH IN FRONT OF AND WITHIN SIGHT

OF THE CONTROLLER – CONSULT LOCAL CODES.

CAUTION

CAUTION

WARNING

CAUTION

Incoming Power

Wires to Motor

Advertising