Xylem IM182 Balanced Flow User Manual

Page 6

Advertising
background image

6

3: INSTALLER PRE-START SELECTIONS
DRIVE SETTINGS AND PROTECTION
Maximum Frequency (Speed) Switch

The Maximum Frequency switch sets the maximum

frequency (motor speed) the controller uses to energize the

motor to either 60 or 80 Hz.
• 60 Hz - Use for matched pump-motor combinations

where the motor HP and pump HP are the same.

Example: 2 HP WE and 2 HP Motor

• 80 Hz - Use for mis-matched pump-motor combinations

where motor HP is larger than the pump HP (typically 2x

larger).

Example: 1 HP WE and 2 HP Motor

• The unit is factory pre-set at 60 Hz.

Dry Well Sensitivity

Selections are High or Low. This function protects the

system from running dry. The selection depends on

several conditions and pump size.
Start with the sensitivity on high and test by running

pump at various flows. If a dry well fault is triggered,

switch to low setting. The unit is factory pre-set at high.
Restart times in minutes are: 1, 10, 20, 30, 60, 60 and

repeating every 60 minutes thereafter.
Example: 1st fault shuts down for 1 minute, next fault

shuts down for 10 minutes, then 20, etc.

Broken Pipe Protection

ON Position - Used for constant pressure systems. The

drive will turn off if the system pressure drops 20 PSI

below the system set point pressure for a minimum of

30 seconds. This fault must be manually reset, it will not

clear automatically, this may prevent property damage if

a pipe breaks.
OFF Position - Use for open discharge situations such as

flushing a tank, filling a pond or tank, or whenever the

system pressure will be 20 psi or more below the system

set point pressure.

Pressure Drop – 5 PSI or 20 PSI

The pressure drop before the pump restarts can be set to

the standard 5 PSI or to 20 PSI.
The 20 PSI setting results in fewer starts for systems with

leaks. It is recommended for irrigation systems. It will

require a tank pre-charge adjustment. See Tank Sizing.

CURRENT LIMIT PROTECTION
Motor Overload Setting Dial

Failure to properly adjust the Motor

Overload Setting before applying power may

damage the motor or wire and void the warranty.

• Use Table 2 to determine which controller and setting to

use. Note that some 200V motors require upsizing to the

next larger controller.

• Set the Motor Overload - Turn the dial pointer to align

with the motor’s service factor amps (SFA) as listed on

the Motor Overload / Current Limit chart. Choose the

amperage value from the Current Limit Settings chart

on UIB that is closest to the SFA listed on the motor

nameplate but not higher.

• See Table 3 or the motor nameplate for Motor Amperage

ratings. The controller limits the output current to the

value selected by this dial. It does this by lowering the

frequency and voltage. If the current does not come

within the selected value by the time the frequency is at

40Hz, the controller will shut down and indicate Bound

Pump error (4 red blinks).

PRESSURE ADJUSTMENT
Pressure Adjustment Pushbuttons

The INCREASE and DECREASE pushbuttons are used

to set the desired pressure. To adjust pressure, press and

hold (do not tap) the button until the desired pressure is

obtained. It may take a full minute to adjust the pressure

from maximum to minimum, please be patient. Pressure can

only be changed when the pump-motor is running.

Controller Status Indicator

(Light Visible Through

Window in Cover)

The controller status indicator light has 3 possible modes:
• Solid green = Standby, pump not running. There is no

water flow or the SWITCH INPUT is open.

• Blinking green = Pump running. There is flow (possibly a

leak) and the SWITCH INPUT terminals are connected to

each other (closed).

• Red = Error/Fault. Light will blink to indicate a particular

fault. See Troubleshooting Section for Fault Codes.

Purging System

Open a valve and turn power on to the controller. If

the system pressure is below the factory preset pressure

setting (50 psi), the status light will begin blinking green

indicating that pump is running. The controller hums

when it is running. This is normal.
It is common for the pump to be air bound at

first, especially with shallow wells. In this case, the

controller will begin testing for a dry well (refer to the

troubleshooting section for a description of Dry Well

Detection).
Once the water is flowing, be sure to open all valves to

purge air from the system.

Checking Rotation

It is possible that the motor is rotating in

the wrong direction. The pump will work

but will have greatly reduced performance if rotating

backwards.
To check rotation, perform the following test:

Connect an amp probe to one of the power supply

wires. Run the system with several valves open and note

the pressure and amps. Leave the valves open, turn the

power off, and wait 5 minutes for the hazardous voltages

to discharge.
Swap red and black motor leads where they connect to

the controller terminal block (NOT L1 and L2).
Turn power back on and let the system pressure

stabilize. Again note the pressure and amps. Whichever

wire position provided the most pressure/flow is the

correct wire position. If there was little difference in the

pressure/flow, then whichever had the lower amp reading

is the correct wire position.
Turn the power off, wait 5 minutes and swap the wires

back if necessary.

3. INSTALLER PRE-START SELECTIONS

WARNING

WARNING

Advertising