User interface board – Xylem IM182 Balanced Flow User Manual

Page 8

Advertising
background image

8

Figure 3: UIB (User Interface Board)

3 Phase Motor

Controller Model ②

Circuit Generator ④

HP

Voltage ①

BF20

BF30

BF50

Breaker ③

(VA)

¾

230

15

2900

200

1

230

3500

200

1½

230

20

4400

200

2

230

6100

200

30

230

3

200

8100

40

5

230

50

13300

200

NOTES:
①

Motor Nameplate must be the same as supply voltage.

②

Shaded areas indicate which controller models can be used with which

motors. Lighter shading indicates combinations where controller will limit

peak performance to 85% of catalog value for pump/motor.

③

Circuit Breaker or Dual Element Time Delay Fuse Size (Amps) protecting

branch circuit supplying controller.

④

Minimum size of single phase 240 V generator required.

Table 2: Controller, Breaker, Generator Sizing

Table 3: Service Factor Amps 3 Phase Motors

230 Volt, 3Ø

200 Volt, 3Ø

HP

CentriPro

Franklin

CentriPro

Franklin

SFA

SFA

SFA

SFA

¾

4.0

3.8

4.5

4.4

1

4.7

4.7

5.5

5.4

1½

6.1

5.9

7.2

6.8

2

7.6

8.1

8.8

9.3

3

10.1

10.9

12

12.5

5

17.5

17.8

20.2

20.5