User interface board – Xylem IM182 Balanced Flow User Manual
Page 8
![background image](/manuals/310494/8/background.png)
8
Figure 3: UIB (User Interface Board)
3 Phase Motor
Controller Model ②
Circuit Generator ④
HP
Voltage ①
BF20
BF30
BF50
Breaker ③
(VA)
¾
230
15
2900
200
1
230
3500
200
1½
230
20
4400
200
2
230
6100
200
30
230
3
200
8100
40
5
230
50
13300
200
NOTES:
①
Motor Nameplate must be the same as supply voltage.
②
Shaded areas indicate which controller models can be used with which
motors. Lighter shading indicates combinations where controller will limit
peak performance to 85% of catalog value for pump/motor.
③
Circuit Breaker or Dual Element Time Delay Fuse Size (Amps) protecting
branch circuit supplying controller.
④
Minimum size of single phase 240 V generator required.
Table 2: Controller, Breaker, Generator Sizing
Table 3: Service Factor Amps 3 Phase Motors
230 Volt, 3Ø
200 Volt, 3Ø
HP
CentriPro
Franklin
CentriPro
Franklin
SFA
SFA
SFA
SFA
¾
4.0
3.8
4.5
4.4
1
4.7
4.7
5.5
5.4
1½
6.1
5.9
7.2
6.8
2
7.6
8.1
8.8
9.3
3
10.1
10.9
12
12.5
5
17.5
17.8
20.2
20.5
USER INTERFACE BOARD
USER INTERFACE BOARD
Drive
Settings /
Protection
Pressure
Adjustment
Pressure
Transducer
Connection
Current Limit Dial
(Motor Overload
Protection)
Switch Input (Over
Pressure Protec-
tion, Level Control)
TRANSDUCER
JUMPER