Xylem IM182 Balanced Flow User Manual

Page 7

Advertising
background image

7

• Ex. On a system with a 50 PSI set point, set the over-pres-

sure switch cut-out at 60 PSI with a typical PRV setting of

75 PSI. In the event the transducer fails at high pressure

the switch will turn the system off before the PRV pops.

• Typical UIB Settings For This Type System:

• 60 or 80 Hertz (depends on pump/motor)
• Dry Well - High (switch to low if it trips while pumping

water)

• Broken Pipe - On
• Pressure Drop - 5 PSI
• Transducer - Connected
• Transducer Jumper - Bottom Position (Factory Setting)
• Pressure Switch Connected to Switch Input

FLOAT SWITCH OPERATION - Filling a Pond or Tank

(Non-Constant Pressure System):

• Connect two wires from a float (level) switch to fill or

empty a tank, pond, etc. The pump will run when the

level switch contacts close. The maximum switch wire

length tested is 200’. The pump will run at maximum

speed when the float switch is closed.

• Typical UIB Settings For This Type System:

• 60 or 80 Hertz (depends on pump/motor)
• Dry Well - High (switch to low if it trips while pumping

water)

• Broken Pipe - Off
• Pressure Drop - 5 or 20 PSI
• Transducer - Not Connected
• Transducer Jumper - Top Position (Installer Must Move)
• Float Switch Connected to Switch Input

FLOAT SWITCH OPERATION - Filling a Pond or Tank

and Constant Pressure System:

• Connect two wires from a float (level) switch to fill or

empty a tank or pond and a pressurized system. The

maximum switch wire length tested is 200’. The pump

will operate at various speeds and try to maintain the set

point pressure. If piping is large and it cannot maintain

set point pressure it will operate at maximum speed.

• Typical UIB Settings:

• 60 or 80 Hertz (depends on pump/motor)
• Dry Well - High (switch to low if it trips while pumping)
• Broken Pipe - On (switch to off if pressure drops by 20

PSI or more)

• Pressure Drop - 5 PSI
• Transducer - Connected
• Transducer Jumper - Bottom Position (Factory Setting)
• Float Switch Connected to Switch Input

Transducer Jumper

Explosion Hazard. Keep jumper in bottom

position whenever a pressure transducer is

used. Failure to do so may cause a pressure transducer error

to be ignored and an over-pressure hazard to result.
For applications not requiring a pressure transducer such

as level control, the transducer can be removed. When

the transducer is not used, the Transducer Jumper must be

placed in the top position to prevent a sensor error. Never

place the jumper in the top position when using a pressure

transducer.

Replace the plastic protective covers on the terminal

block.

Checking for leaks

Constant pressure systems utilizing small tanks run

whenever there is demand. Even small leaks can prevent

a pump from turning off. To check for leaks, close all

valves, turn power off to the controller, and note the

pressure displayed on the pressure gauge. Tap the gauge

to ensure you get an accurate reading.
Wait ten minutes and check the gauge again tapping to

prevent the needle from sticking. If the pressure dropped

then the system may have a leak*.
*If a system is pressurized after having been un-

pressurized, it will continue to expand for several

minutes. This expansion causes the pressure to drop

and can be misinterpreted as a leak. Allow a system to

stabilize for 10 minutes under pressure before

performing the aforementioned leak test.
A spring check valve placed on the pump side of the

tank and transducer will often improve the ability of the

system to shut down.

SWITCH INPUT
Optional Switch Input and Switch Input

Status Light

Log onto www.centripro.com, click on Goulds Pumps or

Red Jacket, click on Electrical Controls Water, click on

Balanced Flow for more detailed examples on using the

Switch Input.

Electrocution Hazard. Opening SWITCH

INPUT does not de-energize controller

or any of its outputs. Always treat wire terminals of this

controller as energized until power supply to the controller

has been removed for 5 minutes.
SWITCH INPUT - for connection of an external switch

or control device used to start and stop the pump. Devices

such as an over-pressure switch, level (float) switch or any

other non-powered switch (time delay, flow, etc.) can be

connected to this input.
The Switch Input terminals have a Jumper Wire installed at

the factory (do not confuse the jumper wire on the Switch

Input with the Transducer Jumper next to the Transducer

Connection Terminals, see Transducer Jumper below).

The Switch Input terminals must be connected (closed) for

the pump to operate. If they are not connected the Switch

Input Status Light (visible inside the enclosure) will be Solid

RED and the Controller Status Light will be Solid GREEN

indicating that the pump-motor is off. Remove the Jumper

Wire when connecting a float or over-pressure switch:
CONSTANT PRESSURE SYSTEM - with an Over-Pressure

Switch:

• Connect two wires from the Load and Lead connections

of a pressure switch to provide over-pressure protection.

In the event the pressure transducer fails, this will prevent

high pressure from damaging piping.

• The over-pressure switch cut-out setting must be a mini-

mum of 10 PSI higher than the system set point pressure.

• Set the over-pressure switch cut-out 5 - 10 PSI lower than

the pressure relief valve (PRV) pop-off pressure. This will

turn the system off before the pressure relief valve opens.

DANGER

DANGER

Advertising