Table 6: Fault Blink Codes

(continued from previous page)

RED LIGHT CODES

Flashes

Controller Status

Description

7 Blinks

Temperature

This fault can be caused by:

• High ambient temperature. The maximum ambient temperature

rating is 122º F (50º C).

• Low ambient temperature. The minimum ambient temperature

rating is -4º F (-20º C).

Check for a fan failure. The fan will turn on when the temperature

inside the controller reaches 140º F (60º C). The fan will turn on for

1 second each time the controller starts the motor. If the fan never

turns on, check fan connections and replace as needed. Ensure that

the external fan intake filter is not blocked or clogged. It can be

removed for cleaning and replacements are available.

8 Blinks

Open Lead

This fault can be caused by:

• Disconnected or broken wire between the controller and motor.

Verify the error by turning power to controller off for 1 minute and

then on. If error persists, motor and wiring between controller and

motor must be checked. Turn power off for 5 minutes. Remove the

three motor wires from the terminal block. Using an ohmmeter,

measure the resistance from phase to phase. A disconnected or

broken wire will be indicated by a high resistance reading (20 ohms

or higher).

9 Blinks

Broken Pipe

This fault can be caused by:

• Pressure 20 PSI below set point for 30 seconds. May be a broken

pipe or tripped pressure relief valve. If 20 PSI or more pressure

drop for 30 seconds is normal for the system, switch the broken

pipe protection off or change system to prevent the pressure drop.

The controller will auto-

matically restart when the

temperature reaches an

acceptable level. If fault

persists contact installer.

The controller will not

restart if displaying this

fault. To clear the fault, turn

off power to the controller,

wait 1 minute, turn on pow-

er to the controller. If fault

persists contact installer.

The controller will not

restart if displaying this

fault. To clear the fault, turn

off power to the controller,

wait 1 minute, turn on pow-

er to the controller. If fault

persists contact installer.

CENTRIPRO LIMITED WARRANTY

This warranty applies to the Balanced Flow Series Controller manufactured by CentriPro.
Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The warranty pe-

riod shall exist for a period of twenty-four (24) months from date of installation or thirty (30) months from date of manufacture, whichever period is shorter.
A dealer who believes that a warranty claim exists must contact the authorized CentriPro distributor from whom the equipment was purchased and furnish

complete details regarding the claim. The distributor is authorized to adjust any warranty claims utilizing the CentriPro Customer Service Department.
The warranty excludes:

(a) Labor, transportation and related costs incurred by the dealer;

(d) Consequential damages of any kind; and,

(b) Reinstallation costs of repaired equipment;

(e) Reimbursement for loss caused by interruption of service.

(c) Reinstallation costs of replacement equipment;
For purposes of this warranty, the following terms have these definitions:

(1) “Distributor” means any individual, partnership, corporation, association, or other legal relationship that stands between CentriPro and the dealer in

purchases, consignments or contracts for sale of the subject equipment.

(2) “Dealer” means any individual, partnership, corporation, association, or other legal relationship which engages in the business of selling or leasing equip-

ment to customers.

(3) “Customer” means any entity who buys or leases the subject equipment from a dealer. The “customer” may mean an individual, partnership, corporation,

limited liability company, association or other legal entity which may engage in any type of business.

THIS WARRANTY EXTENDS TO THE DEALER ONLY.

ITT

CentriPro and the ITT Engineered Blocks Symbol are
registered trademarks and tradenames of ITT Corporation.

SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

IM182 Revision 12 February, 2010

Copyright (c) 2010 ITT Corporation

Engineered for life

Residential & Commercial Water Systems

CentriPro

®

Advertising