Xylem IM182 Balanced Flow User Manual

Page 9

Advertising
background image

9

Scenario

Pressure

Jumper

Switch

Controller

Status

Switch Status

Transducer

Position

Input

Status

Indicator

Indicator

Constant

Bottom

Open

Disabled

Solid Green

Solid Red

pressure operation

Connected

Bottom

Closed

Constant pressure

Blinking green if flow

Off

else solid green

Level or pressure

Not

Top

Open

Disabled

Solid Green

Solid Red

switch control

Connected

Top

Closed

Run Full Speed*

Blinking green

Off

* See description of Maximum Speed Switch and Motor Overload Setting Switch for their effect on Full Speed value.

Table 5: Possible Combinations for TRANSDUCER, JUMPER AND SWITCH INPUT

The lengths in each of the Wire Sizing tables represent 100% of the allowable voltage drop when motor is

running at full load. When sizing wire, the voltage drop of each wire segment must be included. The total

must not exceed 100% of the allowable drop. Take for example a 1.5 HP motor with a distance from Service

Entrance to Controller of 100' and 500' between the Controller and Motor.
• Service Entrance to Controller = 100' of 10 AWG (100/455) = 22 % (455' is from the S.E. to

Controller chart)

• Controller to Motor

= 500' of 12 AWG (500/709) = 71 % (709' is from the Controller to

Motor chart)

Total Drop (must be

≤ 100%) 93 %

If the distance from the Controller to Motor was 600' (600/709) = 85% + 22% = 107%, we would need to

use #10 wire for that segment, ex. 600/1126 = 53% + 22% (for 100' of #10) = 75% which is acceptable.

It is also acceptable to use different wire sizes for the Buried and Well sections of wire.

Service Entrance to Controller

Controller Motor

Copper Wire Size 75ºC Insulation Exposed to a Maximum of 50ºC (122ºF) Ambient Temperature

Input

HP

14

12

10

8

6

4

3

2

1

1/0

2/0

3/0

4/0 250

300

350

400

500

½

366

583

925 1336 2107 3345 4175 5267 6637 8364

¾

279

445

706 1020 1608 2552 3186 4019 5065 6383 8055

1

226

360

571

824 1300 2064 2576 3250 4095 5161 6513 8201

*

286

455

657 1036 1644 2052 2589 3262 4111 5188 6533 8236 9710

2

*

*

331

478

754 1197 1495 1886 2376 2995 3779 4759 5999 7073 8455 9852

3

*

*

246

355

561

890 1111 1401 1766 2225 2808 3536 4458 5256 6283 7321

8343

5

*

*

*

218

343

545

680

858 1081 1363 1720 2165 2730 3219 3847 4483

5109

6348

230V

1 PH

Controller to Motor

Controller Motor

Copper Wire Size 75ºC Insulation Exposed to a Maximum of 50ºC (122ºF) Ambient Temperature

Input

HP

14

12

10

8

6

4

3

2

1

1/0

2/0

3/0

4/0 250

300

350

400

500

½

905 1442 2290 3306 5213 8276

¾

690 1100 1748 2523 3978 6316 7884 9945

1

558

890 1413 2040 3216 5106 6375 8041

445

709 1126 1625 2562 4068 5078 6406 8072

2

324

516

820 1184 1866 2963 3699 4666 5879 7410 9351

3

241

384

609

880 1387 2202 2749 3467 4369 5506 6949 8750

5

*

235

373

539

849 1348 1683 2123 2675 3372 4255 5358 6755 7964 9520

Reduce lengths by 13% for 200 V systems.

* Wire does not meet the N.E.C. ampacity requirement.

Lengths in bold require 90º C wire.

Shading indicates 40º C maximum ambient.

230V

3 PH

Table 4: Wire Sizing

Maximum Cable Lengths in Feet to Limit Voltage Drop to 5% for 230 V Systems