Xylem IM182 Balanced Flow User Manual

Page 11

Advertising
background image

11

Table 6: Fault Blink Codes

(continued on next page)

RED LIGHT CODES

Flashes

Controller Status

Description

3 Blinks

Sensor Fault

This fault can be caused by:

• Disconnected sensor. Disconnect sensor from sensor cable connector and

reconnect to ensure a good connection.

• Disconnected sensor cable lead inside the controller. Check for loose wires

where the sensor cable connects to the circuit board by tugging on each wire.

• Broken wire in the sensor cable.

• Miswired sensor cable. Check that the wires are connected to the correct ter-

minals on the sensor connector. The correct location of the wires is indicated

on the circuit board. B=Black, R=Red, W=White.

• Failed sensor. With the sensor cable connected to the circuit board, measure

the DC voltage between the black and white wires of the sensor cable at

the sensor connector. The voltage measured should be between 0.5Vdc and

4.5Vdc depending on the system pressure, see chart below.

• A vacuum on the sensor (transducer) of 17" Hg or more will cause a sensor

fault, eliminate the vacuum.

4 Blinks

Pump or Motor Bound

This fault can be caused by:

• Installing a 1Ø motor - system requires a 3Ø, 200 or 230 V motor.

• Mechanical binding from debris in pump.

• Electrical failure of the motor.

• Incorrect setting of “MOTOR OVERLOAD SETTING (SFA)” switch.

A false “bound pump” error will be displayed if the switch is set too low.

Verify the error by turning power to controller off for 1 minute and then on.

Pump/Motor must be checked if fault persists.

5 Blinks

Short Circuit

This fault can be caused by:

• Electrical failure of the motor.

• Electrical failure of wiring between controller and motor.

Verify the error by turning power to controller off for 1 minute and then on.

If error persists, motor and wiring between controller and motor must be

checked. Turn power off for 5 minutes. Remove the three motor wires from

the terminal block. Check wiring and motor for shorting phase to phase and

phase to ground. Refer to motor’s manual for information on resistance

readings.

6 Blinks

Ground Fault

This device does not provide personnel protection against

shock. This function is intended for equipment protection

only.

This fault can be caused by:

• Electrical failure of the motor

• Electrical failure of wiring between controller and motor.

• Miswiring of motor cable.

Verify the error by turning power to controller off for 1 minute and then on.

If error persists, motor and wiring between controller and motor must be

checked. Turn power off and wait 5 minutes. Remove the three motor wires

and ground wire from the terminal block. Check wiring and motor for

shorting phase to ground using a megohmmeter (“megger”). A reading less

than 200K Ohms indicates faulty insulation in the motor cable or motor.

Test each to determine fault location.

The controller will not run

if the signal from the

sensor is disconnected or out

of tolerance. The controller

will automatically restart when

the signal is within tolerance. If

fault persists contact installer.

Pressure (PSI)

Sensor Output vs. Applied Pressure

Transducer Output (V

olts DC)

100 PSI Sensor
200 PSI Sensor

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

5

0

25

50

75

100

125

150

175

200

The controller will try to restart the

motor three times before displaying

this fault. To clear the fault, turn off

power to the controller, wait 1 min-

ute, turn on power to the controller.

If fault persists contact installer.

If this fault is detected while

the pump is running, the

controller will attempt to restart

three times before displaying this

fault. To clear the fault, turn off

power to the controller, wait 1 min-

ute, turn on power to the controller.

If fault persists contact installer.

The controller will not restart

if displaying this fault. To clear

the fault, turn off power to the

controller, wait 1 minute, turn

on power to the controller. If

fault persists contact installer.