4 SELECTION GUIDE TO

SELECTION GUIDE TO

SELECTION GUIDE TO

SELECTION GUIDE TO THE CORRECT INSTALLATION

THE CORRECT INSTALLATION

THE CORRECT INSTALLATION

THE CORRECT INSTALLATION

4.1 H

4.1 H

4.1 H

4.1 Hydraulic connection

ydraulic connection

ydraulic connection

ydraulic connection

For MMW model, install an expansion vessel of at least 8 liters to protect the product against water

hammer and to avoid continuous restart of pump in presence of small leaks in the system. For MMA
model, have to install an expansion vessel at least 20 liters. Vessel have to be pre-loaded with air at a
pressure of 0.8 x pressure value set in the inverter. The precharge is performed with zero pressure
system.

Recommendations:

o

Install AQUONTROLLER near the pump; if mounted directly on the pump check there are no
harmful vibrations.

o

For the MMW model, the pipes must be no less than the diameter of AQUONTROLLER
hydraulic.

o

Insert a cartridge filter to protect the hydraulic system and possible AQUONTROLLER (model
MMW) from solid parts in the liquid pumped.

o

For the MMW model, install valves with union upstream and downstream of the inverter so as
to facilitate the eventual isolation and / or removal from the system.



Typical system diagrams

Typical system diagrams

Typical system diagrams

Typical system diagrams
Submersible pumps:

M

P

Shut off valve

Expansion vessel

Electric motor

Pump

Non return valve

Hydrauli filter

Pressure gauge

Pressure transmitter

Impedance coil

S

Float switch

Filter

Aquontroller

M MA

20lt

Filter

8lt

Aquontroller

M MW

M ax 20 mt

S

L max

L max

P

M

P

M

M ax 100 mt

S

mm2

L max

mt

1.5

20

2.5

50

4

100

Fig.5