51

38

Measured Flux

MMW R

N

0

1023

Varie

Number, coded, used to measure the flow.
For example:
0-250 = integrated check valve (MMW) is closed.
1023 = integrated check valve (MMW) fully open.

39

Treshold Flux

MMW RW

N

0

1023

appr. 1023

This parameter is required in order to perform the correct procedure for switching off
the pump when the pressure reaches the nominal value required par. (72).
E.g.: The driver turns off when the measured flow (par 38) is lower than the set
threshold (par 39). If 1023 is also set, the driver stop procedure does not consider the
flow. In this case the AQUONTROLLER version MMA procedure is used.
Note: if set 1023, MMW transforms to MMA

40

TimeMinThreshold

MMA
MMW

RW

sec

1

1200

20

Delay time to enter the condition of "minimum threshold" (par.22), end of curve pump
operation. The pump remains stationary for the time set in par. (16) and attempts are
made to restart at the value set in par. (17).

41

C.Time NoWater

MMA
MMW

R

sec

0

Varie

In the presence of a fault, it displays the delay prior to entering the “No water” (par
42) alarm condition and increases the number of no-water alarms counter, par(24).
Non-return valve closed

42

LackOfWaterTime

MMW RW

sec

1

1200

25

Delay before entering the “No Water" alarm condition with non-return valve closed and
motor running at 50Hz.
The alarm trips when the pressure falls below the minimum threshold (par 22) but
measures zero flow (par 38).

43

f Output (Hz)

MMA
MMW

R

Hz

Varie

Frequency applied to the motor

44

Voltage Motor

MMA
MMW

R

N

0

32767

Varie

Voltage applied to the motor (proprietary unit of measurement: Umax=32767)

45

C.TimeMinThresh.

MMA
MMW

R

sec

0

Par.(40)

Varie

The delay prior to entering the Minimum threshold alarm condition (par 22) and flow
present is displayed. Moto runs at50Hz, non return valve open.

46

Power (Watt)

MMA
MMW

R

W

0

2500

Varie

Pump power input (Par 1).

47

Length Perturb.

MMA

RW

sec

0.1

20

1

When the delay elapses, Delta bar (par 53) checks the pressure value for the set time. If
it remains where it is or increases, the drive stops.

48

Nom MotorCurrent

MMA
MMW

RW

A

0.45

MMW07: 12
MMA07: 12
MMW12: 719
MMA12: 19

4.5

Nominal motor current of the motor (see the motor rating plate). The maximum power
of the AQUONTROLLER (see plate) must not be exceeded. For longer cable length
(>50m) the value can be increased for 10%.

49

t0 PowerSupplied

MMA
MMW

R

0.1x
sec

0

65535

Varie

Displays the total time on supply, expressed in proprietary units. 1 unit = 0.1 seconds.
After 65535 = 1,82 hours the par 50 is increased by one unit.