MMW

sec

MMW Version:
In this condition, the check valve, integrated, is closed, the engine runs at 50Hz and the
system pressure is below the par value of Start. (73)
MMA Version:
The power drops below the maximum power in terms of lack of water par. (54).

26* Motor Power(W)

MMA
MMW

RW

Watt

300

2500

1800

Rated motor power (P1 of motor). This parameter is only used in multiple pump systems
with more than one AQUONTROLLER connected in parallel.

27

Ki (PID)

MMA
MMW

RW

N

0

50

8

Integral coefficient of PID regulator Change this parameter only if system pressure
oscillates.

28

Operat.Mode

MMA
MMW

RW

N

0

2

1

Manual/Automatic Mode
0=Manual
1=Automatic
2= Multi-pump

29

Actual OpMode

MMA
MMW

R

N

0

2

Varie

Displays the driver operating mode.
0=Manual
1=automatic
2= multi-pump

30

f ManualModeOp.

MMA
MMW

R

Hz

0

Par.(1)

Varie

Displays the motor output frequency.

31

PrsSensor Freq..

MMA
MMW

R

Hz

1500

6300

Varie

Displays the current conversion of signal (mA) of sensor to Hz
4mA = 2000Hz approx.

32

PrsSensor Offset

MMA
MMW

RW

Hz

1500

2500

2000

Calibration of the sensor zero pressure
(1500-2500). Change the parameter in the case of incorrect reading of the sensor.

33

PrsSensor Hz/bar

MMA
MMW

RW

Hz/
bar

100

10000

308
MMW
600
MMA

The full scale calibration of the pressure sensor. It also defines the rate of change of
frequency to the motor with respect to the change in pressure of 1 bar.

34

Curr.Pressure

MMA
MMW

R

bar

0.3

MMW07: 7.5
MMA07: 10
MMW12: 7.5
MMA12: 10

Varie

Measured system pressure

35

AC Main (V)

MMA
MMW

R

V

Varie

Driver voltage input

36

LoadCurrent (A)

MMA
MMW

R

A

0.45

15

Varie

Motor output current.

37

Temp.Monitor

MMA
MMW

R

N

0

1023

Varie

Number, coded, used to display and monitor the temperature on the power module.
20 ° C = 397, 30 = 507.40 = 616, 50 = 702 60 = 784 70 = 850 80 = 888 90 =
909.100 ° C = 929.