Xylem Aquontroller User Manual

Page 55

Advertising
background image


55

MMA

Voltage power supply is not correct.
Incorrect parameters par. 48.
The motor cable is longer than 5mt.

Check the setting of the parameter par.48.
Install the impedance coil.
Ensure that there are no conditions of friction or locking of

the impeller.

I2t Protection

MMW
MMA

Electric

The pump works with a liquid too dense or it is partially

blocked.

The pump does not rotate freely due to mechanical

problems.

The value of current absorbed by the pump exceeds the

maximum current tolerable by inverter.

Ensure that there are no conditions of friction or locking of

the impeller.

...STOP CC......

MMW
MMA

Electric

Electric Short circuit condition between Phase/Neutral

and/or Phase/Neutral/Ground in the pump supply line.


Note: Par. 65 is increasing the value and the inverter is
not blocked, or the counter has reached its maximum
value (50) and the inverter is blocked and you need to
reset the alarm.

Remove the short circuit.
Check the proper absortion of the electric motor.


To restore AQUONTROLLER:

Remove power, wait until the display goes off and restore

power.

Reset the alarm in the maintenance menu (par.65).

Low AC Main.....

MMW
MMA

Electric

Supply Voltage AQUONTROLLER too low, less allowable

limits (<170 VAC).

Check the electrical system and restore the values in the range

that is prescribed in the manual AQUONTROLLER.

High AC Main....

MMW
MMA

Electric

Supply Voltage AQUONTROLLER too high, exeeding

allowable limits (>170 VAC).

Check the electrical system and restore the values in the range

that is prescribed in the manual AQUONTROLLER.

Active

MMW
MMA

----

No anomaly. Normal operating condition.

AQUONTROLLER is regulating the system pressure.

Disabled

MMW
MMA

-

AQUONTROLLER is supplied but there is no voltage at

the motor output terminals.

Repeat the Start-up procedure for the installation, Auto-start

setting to ON (par.77).


Nota:

Nota:

Nota:

Nota:
In case of faults, consult the MESSAGE TABLE (paragraph 6).
If none of the proposed solutions solves the problem, contact the Lowara technical assistance service, giving the following information:

Product version (as shown on the display when the appliance is powered).

Product serial number.