Parameter list of the Extended Menù

Parameter list of the Extended Menù

Parameter list of the Extended Menù

Parameter list of the Extended Menù

Rif.

Rif.

Rif.

Rif. Parameter

Parameter

Parameter

Parameter

Model

Model

Model

Model

Read

Read

Read

Read

(R)

(R)

(R)

(R)

Write

Write

Write

Write

(RW)

(RW)

(RW)

(RW)

Unit

Unit

Unit

Unit

Min

Min

Min

Min

Max

Max

Max

Max

Defaul

Defaul

Defaul

Defaul

tttt

Description

Description

Description

Description

00

Password

MMA
MMW


00066
(0074
0)

Password for changing parameters in the Extended Menu - for reading only no
password is needed. If password was set wrong the message: “???password=0…” will
be displayed and values were not changed.

01

fnom. motor

MMA
MMW

RW

Hz

39.99 99.99

45

Rated frequency of motor. This value f(nom) is indicated on the motor rating plate.

02

Language

MMA
MMW

RW

Italian Language selection.

03

f (Umax)

MMA
MMW

RW

Hz

29.99 99.99

50

Frequency applied to the motor to obtain Umax (e.g.: set 50 to obtain 230V at 50 Hz)

04* Configuration

MMA
MMW

RW

N.

0

2

1

This parameter must be set to default value “1”

05

Input Buffer

MMA
MMW

R

N.

0

255

Varie

Read digital inputs

06

Ramp 1 Acceler.

MMA
MMW

RW

sec

0.7

5

1.5

Time required for the output frequency applied to the motor to pass from zero to
maximum frequency.

07

Ramp 2 Deceler.

MMA
MMW

RW

sec

0.7

5

1.5

Time required for the output frequency applied to the motor to pass from maximum
frequency to zero.

08

JOG Frequency

MMA
MMW

RW

Hz

0

Par.(1)

50

Sets the frequency applied to the motor in the manual mode. In the operating mode
(para 28) it must =0

09

Drive State

MMA
MMW

R

0

0

107

Varie

Coded number, used to display driver state information. Examples: 0=off, 1=motor
accelerating, 2=constant speed, 3=deceleration, 4=stopping, 5=stopped, 100=over
current FF. 101=over current FT, 102=under voltage, 103=over voltage, 104=over
temperature, 105=Short circuit shut-down, 106=protected I2T, 107=motor
disconnected.

10

MMA
MMW

R

0

0

104

Varie

Coded number, used to display hydraulic system information and measurements.
0=Disabled, 1=Stop, 2=Run, 100=No water, 101=Insufficient pressure, 102=Pressure
sensor fault, 103=Water hammering.

11

fmin /MotorStop

MMA

RW

Hz

0

Par.(1)

10

Minimum permitted motor frequency. The driver shuts down below this value. Active if
different from 0.

12

Drive ResetTime

MMA

RW

sec

0.1

100

10

Delay between one motor start and the next following a driver fault. Driver 10X states