3.7 Connecting the DC Output Connection

1. Locate and remove the safety shroud. The shroud is held in place with two thumbscrews.

Shroud Location

2. Strip the user-supplied DC load wires 3/4". Loosen the 3/16" Allen screws and insert the

DC load wires. Torque to 120 in-lbs and replace the safety shroud.

Negative DC

Load Connection

Fig. 3-8, DC Output Safety Shroud

Fig, 3-9, DC Output Block

Positive DC

Load Connection