745-020-B0-003, Rev. C

77

Fig. 8-7, 48VDC Charger Control Interface Connector

Pin

Description

Function

1

Line 1, 120VAC AC Line
Sense

The Line side that powers the ECM and Power
PCB, and provides AC line sense to start the
APU.

2

Line 2, Neutral

The Neutral side of the incoming line power.

8.8 ECM AC Line Sense 120/240V Interface

The interface control (J6) is a 2-pin (1x2 row) Mini Mate-’N’-Lok style connector.

REAR
VIEW

REAR

VIEW

WIRE

SIDE

J6

Fig. 8-8, ECM AC Line Sense, 120/240V Interface

Pin Description

Function

1

Control Positive

Connects pin 1 & 2 together, turning the Charger ON, i.e. Closed
(LOW signal)

2

Control Negative

Charger control common return

8.0 Interconnection,

continued

8.7 48VDC Charger Control Interface Connector

The Battery Charger Control Interface Connector is connected between the charger
module and ECM as shown. The interface control is a terminal block 2-position plug-in
connector.

Pin 1

Pin 2

Advertising